FIR06-00469
| INSP-Final Inspection | 4/20/2009 | 4/21/2009 | 4/21/2009 4:05:40 PM | A | CANC |
|
|
The inspection has been rescheduled for tomorrow due to time constraints today.
|
FIR09-00125
| INSP-Final Inspection | 4/21/2009 | 4/21/2009 | 4/21/2009 3:51:16 PM | P | PASS |
|
|
Permit finaled
|
BLD08-02170
| FIRE-Final Inspection | 4/20/2009 | 4/21/2009 | 4/21/2009 3:48:59 PM | A | PART |
|
|
All life safety items are passed but only a temporary occupancy was given until the project related fire alarm permit is finaled.
|
BLD08-01015
| FIRE-Final Inspection | 4/21/2009 | 4/21/2009 | 4/21/2009 1:49:05 PM | P | FAIL |
|
|
Provide the street address on both sides of the building as discussed, provide and mount the fire extinguisher as discussed, provide the occupant load sign (49) as discussed and provide modifications as discussed for the hvac system for proper placement of the duct smoke detector with a remote annunciator or provide verification that the hvac unit in question does not exceed 2,000cfm.
|
FIR07-01031
| INSP-Sprinkler Rough-in | 4/20/2009 | 4/21/2009 | 4/21/2009 12:02:44 PM | A | PASS |
|
|
The sprinkler piping above the existing sheet rock ceiling is ok to cover. The sprinkler piping as installed does not match the city approved plans and will need to be resubmitted with all of the other changes for approval prior to final.
|
FIR08-00736
| INSP-Final Inspection | 4/20/2009 | 4/21/2009 | 4/21/2009 11:01:22 AM | A | PART |
|
|
Permit finaled
|
FIR09-00019
| INSP-Final Inspection | 4/20/2009 | 4/21/2009 | 4/21/2009 10:26:06 AM | A | FAIL |
|
|
The flow switches still need to be tested, the new trouble signal did not report to the DMP panel and the horn/strobe circuit shut off on its own twice.
|
FIR09-00177
| INSP-Sprinkler Rough-in/Hydro | 4/21/2009 | 4/21/2009 | 4/21/2009 9:41:04 AM | A | CANC |
|
|
The hydro test is being cancelled due to the locked united water valve
|
FIR09-00177
| INSP-Supply line flush | 4/20/2009 | 4/21/2009 | 4/21/2009 9:37:30 AM | A | FAIL |
|
|
The United Water valve lock was still in place so the flush could not be completed.
|
FIR09-00177
| INSP-Sprinkler Rough-in/Hydro | 4/20/2009 | 4/21/2009 | 4/21/2009 9:08:37 AM | P | CANC |
|
|