Inspections for the day of: Wednesday, April 21, 2010.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00845 Permanent Service4/21/20104/21/20104/21/2010 4:51:51 PMPPASS
conditional- pending am inspection on 4-22-10 per discussion with contractor and #370. p/s o/h rec ok, no esc this project
ESC10-00192 General Inspection4/21/20104/21/20104/21/2010 3:03:28 PMPPASS
ESC10-00013 General Inspection4/21/20104/21/20104/21/2010 3:02:56 PMPPASS
ELE10-00833 Permanent Service4/21/20104/21/20104/21/2010 3:01:03 PMPPASS
Andy Phone #: ###-#### p/s u/g n ok, no esc this project
ESC09-00069 General Inspection4/21/20104/21/20104/21/2010 2:35:05 PMPPASS
ELE10-00836 Rough-In Permanent Service4/21/20104/21/20104/21/2010 1:56:19 PMPPASS
James Phone #: ###-#### ri ok, p/s u/g n ok, no esc this project
ELE10-00839 Final4/21/20104/21/20104/21/2010 1:14:59 PMPPART
final for garage/ underground for electrical conduit Inspection requested from web by: TOM BICANDI Phone #: ###-#### ok to cover u/g only, will call for ri tomorrow
ELE10-00680 Electrical Rough-In4/20/20104/21/20104/21/2010 10:46:53 AMAPASS
underslab branch circuit rough-in Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover slab inside building
ELE10-00793 Electrical Rough-In4/20/20104/21/20104/21/2010 10:16:19 AMAFAIL
Inspection requested from web by: Joe Thomas Phone #: ###-#### called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 300.14 shall provide 6" free conductor length at boxes, 334.23 shall protect cable within 6' of attic access, 250.148 shall ground metal boxes, BCC shall install boxes, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-00423 Permanent Service4/20/20104/21/20104/21/2010 9:29:01 AMAFAIL
Inspection requested from web by: Clint Tate Phone #: ###-#### met electrician, only 1 service allowed per building per NEC 230, no esc this project
ELE10-00022 Final4/20/20104/21/20104/21/2010 8:55:25 AMAPASS
Rick- call 30 mins prior to going to meet Phone #: ###-#### correrctions made, ok to final, no esc this project
ELE10-00726 Electrical Rough-In4/20/20104/21/20104/21/2010 8:19:26 AMAPASS
Ceiling cover.
I will be in the lobby at 8:00 am.
Thanks,
Ron Inspection requested from web by: Ron Zimmerman Phone #: ###-#### ceilings only ok to cover 4 areas, no esc this project