ELE10-00845
| Permanent Service | 4/21/2010 | 4/21/2010 | 4/21/2010 4:51:51 PM | P | PASS |
|
|
conditional- pending am inspection on 4-22-10 per discussion with contractor and #370. p/s o/h rec ok, no esc this project
|
ESC10-00192
| General Inspection | 4/21/2010 | 4/21/2010 | 4/21/2010 3:03:28 PM | P | PASS |
|
|
|
ESC10-00013
| General Inspection | 4/21/2010 | 4/21/2010 | 4/21/2010 3:02:56 PM | P | PASS |
|
|
|
ELE10-00833
| Permanent Service | 4/21/2010 | 4/21/2010 | 4/21/2010 3:01:03 PM | P | PASS |
|
|
Andy Phone #: ###-#### p/s u/g n ok, no esc this project
|
ESC09-00069
| General Inspection | 4/21/2010 | 4/21/2010 | 4/21/2010 2:35:05 PM | P | PASS |
|
|
|
ELE10-00836
| Rough-In Permanent Service | 4/21/2010 | 4/21/2010 | 4/21/2010 1:56:19 PM | P | PASS |
|
|
James Phone #: ###-#### ri ok, p/s u/g n ok, no esc this project
|
ELE10-00839
| Final | 4/21/2010 | 4/21/2010 | 4/21/2010 1:14:59 PM | P | PART |
|
|
final for garage/ underground for electrical conduit Inspection requested from web by: TOM BICANDI Phone #: ###-#### ok to cover u/g only, will call for ri tomorrow
|
ELE10-00680
| Electrical Rough-In | 4/20/2010 | 4/21/2010 | 4/21/2010 10:46:53 AM | A | PASS |
|
|
underslab branch circuit rough-in Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover slab inside building
|
ELE10-00793
| Electrical Rough-In | 4/20/2010 | 4/21/2010 | 4/21/2010 10:16:19 AM | A | FAIL |
|
|
Inspection requested from web by: Joe Thomas Phone #: ###-#### called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 300.14 shall provide 6" free conductor length at boxes, 334.23 shall protect cable within 6' of attic access, 250.148 shall ground metal boxes, BCC shall install boxes, NOTE corrections shall be made within 5 working days or further action will be taken
|
ELE10-00423
| Permanent Service | 4/20/2010 | 4/21/2010 | 4/21/2010 9:29:01 AM | A | FAIL |
|
|
Inspection requested from web by: Clint Tate Phone #: ###-#### met electrician, only 1 service allowed per building per NEC 230, no esc this project
|
ELE10-00022
| Final | 4/20/2010 | 4/21/2010 | 4/21/2010 8:55:25 AM | A | PASS |
|
|
Rick- call 30 mins prior to going to meet Phone #: ###-#### correrctions made, ok to final, no esc this project
|
ELE10-00726
| Electrical Rough-In | 4/20/2010 | 4/21/2010 | 4/21/2010 8:19:26 AM | A | PASS |
|
|
Ceiling cover. I will be in the lobby at 8:00 am. Thanks, Ron Inspection requested from web by: Ron Zimmerman Phone #: ###-#### ceilings only ok to cover 4 areas, no esc this project
|