Inspections for the day of: Thursday, April 21, 2011.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00303 ELE-Aging Inspection4/21/20114/21/20114/25/2011 3:19:03 PM DONE
see final
ELE11-00286 ELE-Aging Inspection4/21/20114/21/20114/25/2011 3:17:17 PM DONE
still under construction
GCE11-00042 GCE-Final4/20/20114/21/20114/22/2011 1:34:33 PMAPASS
FinalKen @ ###-#### ok final
GCE11-00042 GCE-Permanent Service4/20/20114/21/20114/22/2011 11:36:15 AMACANC
Perm ServiceKen @ ###-####Call in advance see 4/22/11 response
ELE11-00735 Temporary Service4/21/20114/21/20114/21/2011 4:02:20 PMPFAIL
Service inspection request-contact is Jake Chouinard ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell met with contractor, gave corrections, add bond bushings, phase tape and color, length of neutral conductor for parallel conductors, fuse sizes
ELE11-00785 Rough-In Permanent Service4/21/20114/21/20114/21/2011 2:30:43 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman called, left correction notice, NEC 250.86 shall provide grounding for metal boxes, 330.30(B) shall secure mc cable within 12" of box
ELE11-00772 Electrical Rough-In4/21/20114/21/20114/21/2011 12:24:00 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by kendall bender called, left correction notice, NEC 210.8(B)(5) receptacles within 6' of sink shall be gfci protected, 300.11(B) (C) shall not support cable wiring from other cables, BCC shall not cover any wiring prior to inspection- no devices installed
GCE11-00045 GCE-Rough-In4/20/20114/21/20114/21/2011 10:02:43 AMAPASS
Rough-InPat @ ###-####Call in advance ri ok
ELE10-01493 Final4/20/20114/21/20114/21/2011 9:13:20 AMACANC
Van please call 30 min before going out Phone #: ###-#### see ri
ELE10-01493 Electrical Rough-In4/21/20114/21/20114/21/2011 9:05:13 AMAPART
Van please call 30 min before going out Phone #: ###-#### ok cover upstairs and entry ceiling, need to see fireplace wall
ELE11-00453 Final4/20/20114/21/20114/21/2011 8:52:05 AMAPART
tim Phone #: ###-#### signed t/o card pending office furniture inspection
ELE11-00763 Electrical Rough-In4/20/20114/21/20114/21/2011 8:16:31 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Dan Rohl ri ok
ELE11-00685 Final4/20/20114/21/20114/20/2011 11:32:57 AMACANC
This is a final inspection please. We would like an 8:00 am inspection if possible. Contact is Bob Callahn. Please call Bob when you are on your way to the site. Thank you so much. Phone #: ###-#### >> Inspection requested via web by Laura Longshaw Inspection cancelled from web by: Laura Longshaw