FIR11-00169
| INSP-Final Inspection | 4/21/2011 | 4/21/2011 | 4/21/2011 3:44:03 PM | P | FAIL |
|
|
Can't final until the ceiling tile has been installed.
|
FIR11-00169
| INSP-Sprinkler Rough-in | 4/21/2011 | 4/21/2011 | 4/21/2011 3:35:05 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR11-00168
| INSP-Final Inspection | 4/21/2011 | 4/21/2011 | 4/21/2011 3:01:22 PM | P | FAIL |
|
|
All items tested ok but the signals sent out report a general fire and supervisory signals for both the 358 and 370 addresses. The signal has to be specific for the address. Signals need to be resent from both buildings to verify corrections. The duct smoke detector was missing the sample tube and was installed while I waited. The tamper switch on the PIV was installed backwards and wired backwards and was also repaired while I waited.
|
FIR10-00542
| INSP-Final Inspection | 4/21/2011 | 4/21/2011 | 4/21/2011 2:57:00 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00543
| INSP-Final Inspection | 4/21/2011 | 4/21/2011 | 4/21/2011 2:31:50 PM | P | PASS |
|
|
Permit finaled
|
FIR39-00017
| FIR-Aging Inspection | 4/21/2011 | 4/21/2011 | 4/21/2011 11:18:51 AM | | PASS |
|
|
|
BLD10-01261
| FIRE-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 10:23:32 AM | A | FAIL |
|
|
Life safety will be ok to final when the project related fire alarm and fire sprinkler permits are finaled. No hazardous materials are currently being stored.
|
BLD10-01256
| FIRE-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 10:22:26 AM | A | PASS |
|
|
life safety passed
|
FIR10-00513
| INSP-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 10:20:09 AM | A | CANC |
|
|
Unable to final until the interconnections with the fire alarm panel can be tested.
|
FIR11-00168
| INSP-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 10:19:12 AM | A | FAIL |
|
|
Installation does not match plans. The modules that were to be removed are still installed. Also the the wire between the two buildings is supposed to meet requirements in NEC article 800 and it does not. No testing was performed.
|
BLD11-00058
| FIRE-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 9:59:35 AM | A | PASS |
|
|
life safety passed
|
FIR11-00094
| INSP-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 9:59:07 AM | A | PASS |
|
|
permit finaled
|
BLD11-00375
| FIRE-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 8:16:02 AM | A | PASS |
|
|
life safety passed
|