Inspections for the day of: Thursday, April 21, 2011.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00169 INSP-Final Inspection4/21/20114/21/20114/21/2011 3:44:03 PMPFAIL
Can't final until the ceiling tile has been installed.
FIR11-00169 INSP-Sprinkler Rough-in4/21/20114/21/20114/21/2011 3:35:05 PMPPASS
Rough-in passed. Piping can be covered.
FIR11-00168 INSP-Final Inspection4/21/20114/21/20114/21/2011 3:01:22 PMPFAIL
All items tested ok but the signals sent out report a general fire and supervisory signals for both the 358 and 370 addresses. The signal has to be specific for the address. Signals need to be resent from both buildings to verify corrections. The duct smoke detector was missing the sample tube and was installed while I waited. The tamper switch on the PIV was installed backwards and wired backwards and was also repaired while I waited.
FIR10-00542 INSP-Final Inspection4/21/20114/21/20114/21/2011 2:57:00 PMPPASS
Permit finaled
FIR10-00543 INSP-Final Inspection4/21/20114/21/20114/21/2011 2:31:50 PMPPASS
Permit finaled
FIR39-00017 FIR-Aging Inspection4/21/20114/21/20114/21/2011 11:18:51 AM PASS
BLD10-01261 FIRE-Final Inspection4/20/20114/21/20114/21/2011 10:23:32 AMAFAIL
Life safety will be ok to final when the project related fire alarm and fire sprinkler permits are finaled. No hazardous materials are currently being stored.
BLD10-01256 FIRE-Final Inspection4/20/20114/21/20114/21/2011 10:22:26 AMAPASS
life safety passed
FIR10-00513 INSP-Final Inspection4/20/20114/21/20114/21/2011 10:20:09 AMACANC
Unable to final until the interconnections with the fire alarm panel can be tested.
FIR11-00168 INSP-Final Inspection4/20/20114/21/20114/21/2011 10:19:12 AMAFAIL
Installation does not match plans. The modules that were to be removed are still installed. Also the the wire between the two buildings is supposed to meet requirements in NEC article 800 and it does not. No testing was performed.
BLD11-00058 FIRE-Final Inspection4/20/20114/21/20114/21/2011 9:59:35 AMAPASS
life safety passed
FIR11-00094 INSP-Final Inspection4/20/20114/21/20114/21/2011 9:59:07 AMAPASS
permit finaled
BLD11-00375 FIRE-Final Inspection4/20/20114/21/20114/21/2011 8:16:02 AMAPASS
life safety passed