FIR14-00362
| INSP-Sprinkler Rough-in/Hydro | 4/21/2015 | 4/21/2015 | 4/23/2015 9:17:12 AM | P | CANC |
|
|
Cancelled overbooked, rescheduled for later date.
|
FIR14-00070
| INSP-Supply line flush | 4/21/2015 | 4/21/2015 | 4/23/2015 9:16:22 AM | P | CANC |
|
|
Cancelled overbooked, rescheduled for later date.
|
BLD15-00070
| FIRE-Final Inspection | 4/21/2015 | 4/21/2015 | 4/21/2015 5:09:54 PM | P | DEFR |
|
|
Unable to accomodate due to loaded scheduled, Tried to reach at 420,
|
NAF14-00022
| INSP-Sprinkler Rough-in/Hydro | 4/21/2015 | 4/21/2015 | 4/21/2015 4:35:44 PM | A | PART |
|
|
Scope of work good to tent with the following exceptions. Heads are missing in mud room and over water heater closet on first floor, per plan. Provide heads or justification for exception according to NFPA 13D. **Per phone discussion with Anthony, hallway head provides exceptable coverage to mudroom in accordance with NFPA 13D 8.2. Additionally water heater is no longer located in that closet so head no longer required since space is less than 24 sqft per chapter 6.
Items remaining, tank requires hose bib to main water supply and flow switch to be tested once hooked into alarm system NACFR 2008-013
|
BLD15-01203
| FIRE-Final Inspection | 4/20/2015 | 4/21/2015 | 4/21/2015 2:24:18 PM | A | PASS |
|
|
Life Safety Pass. Tenant to obtain and mount fire extinguisher prior to building final. Bldg inspector please verify.
|
FIR15-00055
| INSP-Final Inspection | 4/20/2015 | 4/21/2015 | 4/21/2015 1:04:45 PM | A | PASS |
|
|
Scope of work complete. Verified coverage to west side completed satisfactory. Permit Finaled.
|
BLD14-03605
| FIRE-Final Inspection | 4/20/2015 | 4/21/2015 | 4/21/2015 11:59:21 AM | P | NR |
|
|
Alarm permit and hood suppression to be finaled before bldg fire life safety final inspection.
|
FIR14-00529
| INSP-Supply line flush | 4/20/2015 | 4/21/2015 | 4/21/2015 10:45:20 AM | A | PART |
|
|
Supply line flush completed satisfactory.
|
FIR15-00229
| INSP-Sprinkler Rough-in/Hydro | 4/20/2015 | 4/21/2015 | 4/21/2015 10:15:10 AM | A | PART |
|
|
Verified breakroom coverage satisfactory and last drop in corner of cloud ok to cover. Slight sprinkler head adjustments in offices ok to cover.
|
FIR15-00125
| INSP-Final Inspection | 4/20/2015 | 4/21/2015 | 4/21/2015 8:13:02 AM | A | CANC |
|
|
Robert is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|