Inspections for the day of: Tuesday, April 21, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00362 INSP-Sprinkler Rough-in/Hydro4/21/20154/21/20154/23/2015 9:17:12 AMPCANC
Cancelled overbooked, rescheduled for later date.
FIR14-00070 INSP-Supply line flush4/21/20154/21/20154/23/2015 9:16:22 AMPCANC
Cancelled overbooked, rescheduled for later date.
BLD15-00070 FIRE-Final Inspection4/21/20154/21/20154/21/2015 5:09:54 PMPDEFR
Unable to accomodate due to loaded scheduled, Tried to reach at 420,
NAF14-00022 INSP-Sprinkler Rough-in/Hydro4/21/20154/21/20154/21/2015 4:35:44 PMAPART
Scope of work good to tent with the following exceptions. Heads are missing in mud room and over water heater closet on first floor, per plan. Provide heads or justification for exception according to NFPA 13D. **Per phone discussion with Anthony, hallway head provides exceptable coverage to mudroom in accordance with NFPA 13D 8.2. Additionally water heater is no longer located in that closet so head no longer required since space is less than 24 sqft per chapter 6.

Items remaining, tank requires hose bib to main water supply and flow switch to be tested once hooked into alarm system NACFR 2008-013
BLD15-01203 FIRE-Final Inspection4/20/20154/21/20154/21/2015 2:24:18 PMAPASS
Life Safety Pass. Tenant to obtain and mount fire extinguisher prior to building final. Bldg inspector please verify.
FIR15-00055 INSP-Final Inspection4/20/20154/21/20154/21/2015 1:04:45 PMAPASS
Scope of work complete. Verified coverage to west side completed satisfactory. Permit Finaled.
BLD14-03605 FIRE-Final Inspection4/20/20154/21/20154/21/2015 11:59:21 AMPNR
Alarm permit and hood suppression to be finaled before bldg fire life safety final inspection.
FIR14-00529 INSP-Supply line flush4/20/20154/21/20154/21/2015 10:45:20 AMAPART
Supply line flush completed satisfactory.
FIR15-00229 INSP-Sprinkler Rough-in/Hydro4/20/20154/21/20154/21/2015 10:15:10 AMAPART
Verified breakroom coverage satisfactory and last drop in corner of cloud ok to cover. Slight sprinkler head adjustments in offices ok to cover.
FIR15-00125 INSP-Final Inspection4/20/20154/21/20154/21/2015 8:13:02 AMACANC
Robert is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus