Inspections for the day of: Thursday, April 21, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00028 INSP-Sprinkler Rough-in/Hydro4/18/20164/21/20164/22/2016 9:37:11 AMPPART
200 psi hydrostatic test complete for overhead fire sprinkler piping for all levels. Rough to cover inspection complete for overhead fire sprinkler piping on 1st and 2nd level, 1st and 2nd level approved for cover with exception to piping that is ran through breeze-way, this piping cannot be covered until proper freeze protection is installed and inspected. Partial cover approved for 3rd level fire sprinkler piping, fire sprinkler piping that is not in attic spaces approved for cover with exception to breeze-way piping. Fire sprinkler piping in attic spaces on 3rd level and 4th level cannot be covered until tenting inspection is completed and approved. Fire sprinkler piping crosses the entry corridor on each level, these area's cannot be covered until proper heating/ventilation is provided to keep fire sprinkler piping from freezing through the breeze-way (As addressed and stated on city approved drawings)
BLD14-03175 FIRE-Final Inspection4/21/20164/21/20164/21/2016 4:33:03 PMPPASS
Final fire sprinkler inspections complete, final fire pump relocation inspections complete, final fire alarm inspections complete. Fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR15-00185 INSP-Final Inspection4/21/20164/21/20164/21/2016 4:29:55 PMPPASS
Final fire alarm inspection passed/complete
FIR16-00218 INSP-Sprinkler Rough-in/Hydro4/18/20164/21/20164/21/2016 3:03:15 PMPPASS
Rough in inspection for building standpipe complete. 200 psi hydrostatic test for building standpipe complete.
BLD15-02346 FIRE-Final Inspection4/20/20164/21/20164/21/2016 11:22:07 AMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR15-00794 INSP-Final Inspection4/21/20164/21/20164/21/2016 11:20:04 AMPPASS
Final fire alarm inspection passed/complete
FIR16-00116 INSP-Supply line flush4/21/20164/21/20164/21/2016 11:00:45 AMPDONE
Underground main line flush complete
FIR15-00121 INSP-Supply line flush4/20/20164/21/20164/21/2016 10:59:47 AMACANC
Inspection request cancelled, incorrect FIR permit request
FIR15-00329 INSP-Sprinkler Rough-in4/21/20164/21/20164/21/2016 9:16:46 AMAPART
South supply main post indicator valve relocated to line up with tree location, underground inspection for relocation passed/complete. Relocation for north post indicator will be completed at later date.