BLD17-00973
| FIRE-Final Inspection | 4/20/2017 | 4/21/2017 | 4/21/2017 12:55:02 PM | A | FAIL |
|
|
All items corrected except I still need verification of the annual sprinkler inspection
|
FIR16-00293
| INSP-Alarm Testing | 4/21/2017 | 4/21/2017 | 4/21/2017 12:45:00 PM | P | DONE |
|
|
Phase II alarm testing passed. One wall mount strobe at the east stairs is mounted too low and will be adjusted for verification at the next inspection
|
NAF17-00011
| INSP-Final | 4/20/2017 | 4/21/2017 | 4/21/2017 10:26:14 AM | A | PART |
|
|
A temporary for life safety, for 30 days, is being given with Scott's approval until the two thumbturn dead bolts are removed and ADA compliant hardware is installed on the new office door. Also per previous conference with Scott suppression systems will be required for the Powder Coating and Paint Booth operations. This work will require separate permits. The use of these booths is not allowed until approved by the AHJ.
|
BLD17-00149
| FIRE-Final Inspection | 4/20/2017 | 4/21/2017 | 4/21/2017 9:24:43 AM | A | PART |
|
|
A temporary occupancy is being given on the life safety until the project related fire alarm permit is addressed. While testing the fire alarm system modifications I noted that there are two different temporal cadences and solid tone horns all going at the same time. This is in both the tenant areas and the common/egress/core areas of the building which may include the second floor which is accessable by an open stair well. All notification devices are to sync both visually and audibly. This condition needs to be repaired or an upgrade agreement sought with the Boise Fire Dept as discussed.
|
FIR17-00145
| INSP-Final Inspection | 4/20/2017 | 4/21/2017 | 4/21/2017 9:23:51 AM | A | PART |
|
|
A temporary occupancy is being given. While testing the fire alarm system modifications I noted that there are two different temporal cadences and solid tone horns all going at the same time. This is in both the tenant areas and the common/egress/core areas of the building which may include the second floor which is accessable by an open stair well. All notification devices are to sync both visually and audibly. This condition needs to be repaired or an upgrade agreement sought with the Boise Fire Dept as discussed.
|
FIR16-00823
| INSP-Sprinkler Rough-in | 4/20/2017 | 4/21/2017 | 4/21/2017 9:09:06 AM | A | PASS |
|
|
Remaining sprinkler piping is ok to cover
|
FIR17-00085
| INSP-Final Inspection | 4/21/2017 | 4/21/2017 | 4/21/2017 8:31:30 AM | A | PASS |
|
|
Permit finaled
|
FIR16-00711
| INSP-Final Inspection | 4/20/2017 | 4/21/2017 | 4/21/2017 8:31:03 AM | A | FAIL |
|
|
The notification devices with-in the tenant space have been corrected and test. But the notification devices in the path of egress have not been corrected as per email requirement from the fire dept. Email forwarded to Nathan with Simplex
|