Inspections for the day of: Friday, April 22, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00723 Final4/21/20054/22/20054/22/2005 12:00:00 AMAFAIL
please call 30 min prior to inspection///gary; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called left message, left corr notice, 250.130(C) recpts shall use grounding means, 404.9 switches shall have faceplates installed 4/22/2005 10:30:46 AM
ELE05-01364 Temporary Service4/21/20054/22/20054/22/2005 12:00:00 AMAFAIL
###-#### - ryan no temp at site 4/22/2005 10:48:21 AM
ELE05-00524 Final4/21/20054/22/20054/22/2005 12:00:00 AMAPASS
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final 4/22/2005 8:02:34 AM
ELE05-01367 Rough-In Permanent Service4/21/20054/22/20054/22/2005 12:00:00 AMAFAIL
chad ###-#### called, left message, service not ready, no grounding, 300.4(A)(1)&(D) shall provide nail plates and 1 1/4" all areas from inside and outside of framing members, 21.52(A)(2) wall space by front door shall have recpt, 314.3 nonmetallic boxes shall be listed to be used with metal raceways, 314.20 boxes shall be flush with finished surface, 314.17 openings shall be closed BCC shall have approved set of plans on job and job ID sticker 4/22/2005 9:56:50 AM
ELE05-00640 Final4/21/20054/22/20054/22/2005 12:00:00 AMAPASS
jessie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final 4/22/2005 8:29:49 AM
ELE05-01370 Electrical Rough-In4/21/20054/22/20054/22/2005 12:00:00 AMAPASS
STEVE COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ric walls only ok 4/22/2005 8:54:34 AM
ELE05-01364 Temporary Service4/22/20054/22/20054/22/2005 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen t/s u/g n ok 4/22/2005 2:51:55 PM
ELE04-03161 Electrical Rough-In4/22/20054/22/20054/22/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 4/22/2005 at 9:15:48 AM. Contact: ###-####. ok to cover 2 bath and janitor closet clg only 4/22/2005 12:40:15 PM
ELE05-00998 Final4/22/20054/22/20054/22/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 4/22/2005 at 9:26:06 AM. Contact: ###-####. called contr, left corr notice, 110.26(A)(1) depth of working space shall be 3', minimum, 110.26(A)(2) width of working space shall be 30", minimum 4/22/2005 2:31:42 PM
ELE05-00132 Final4/22/20054/22/20054/22/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 4/22/2005 at 9:38:06 AM. Contact: ###-####. called contr about rear rcpt, sheetrock on 1 recpt and sprklr pipe. ok to final 4/22/2005 1:54:05 PM
ELE05-01229 Temporary Service4/22/20054/22/20054/22/2005 12:00:00 AMPPASS
ben; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok 4/22/2005 3:05:33 PM
ELE05-00903 Electrical Rough-In4/22/20054/22/20054/22/2005 12:00:00 AMPNR
ceiling inspection please///james; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ceilings not ready, borders ok except where j-box . 4/22/2005 4:22:41 PM
ELE05-00010 Final4/20/20054/22/20054/21/2005 5:27:32 PMPCANC
We installed a new 20 amp 120 volt circuit to a new receptacle for the above-the-range microwave.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell Inspection cancelled from web by: Dan Mitchell