ELE05-00723
| Final | 4/21/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | A | FAIL |
|
|
please call 30 min prior to inspection///gary; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called left message, left corr notice, 250.130(C) recpts shall use grounding means, 404.9 switches shall have faceplates installed 4/22/2005 10:30:46 AM
|
ELE05-01364
| Temporary Service | 4/21/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | A | FAIL |
|
|
###-#### - ryan no temp at site 4/22/2005 10:48:21 AM
|
ELE05-00524
| Final | 4/21/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | A | PASS |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final 4/22/2005 8:02:34 AM
|
ELE05-01367
| Rough-In Permanent Service | 4/21/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | A | FAIL |
|
|
chad ###-#### called, left message, service not ready, no grounding, 300.4(A)(1)&(D) shall provide nail plates and 1 1/4" all areas from inside and outside of framing members, 21.52(A)(2) wall space by front door shall have recpt, 314.3 nonmetallic boxes shall be listed to be used with metal raceways, 314.20 boxes shall be flush with finished surface, 314.17 openings shall be closed BCC shall have approved set of plans on job and job ID sticker 4/22/2005 9:56:50 AM
|
ELE05-00640
| Final | 4/21/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | A | PASS |
|
|
jessie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final 4/22/2005 8:29:49 AM
|
ELE05-01370
| Electrical Rough-In | 4/21/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | A | PASS |
|
|
STEVE COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ric walls only ok 4/22/2005 8:54:34 AM
|
ELE05-01364
| Temporary Service | 4/22/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen t/s u/g n ok 4/22/2005 2:51:55 PM
|
ELE04-03161
| Electrical Rough-In | 4/22/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/22/2005 at 9:15:48 AM. Contact: ###-####. ok to cover 2 bath and janitor closet clg only 4/22/2005 12:40:15 PM
|
ELE05-00998
| Final | 4/22/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/22/2005 at 9:26:06 AM. Contact: ###-####. called contr, left corr notice, 110.26(A)(1) depth of working space shall be 3', minimum, 110.26(A)(2) width of working space shall be 30", minimum 4/22/2005 2:31:42 PM
|
ELE05-00132
| Final | 4/22/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/22/2005 at 9:38:06 AM. Contact: ###-####. called contr about rear rcpt, sheetrock on 1 recpt and sprklr pipe. ok to final 4/22/2005 1:54:05 PM
|
ELE05-01229
| Temporary Service | 4/22/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | P | PASS |
|
|
ben; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok 4/22/2005 3:05:33 PM
|
ELE05-00903
| Electrical Rough-In | 4/22/2005 | 4/22/2005 | 4/22/2005 12:00:00 AM | P | NR |
|
|
ceiling inspection please///james; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ceilings not ready, borders ok except where j-box . 4/22/2005 4:22:41 PM
|
ELE05-00010
| Final | 4/20/2005 | 4/22/2005 | 4/21/2005 5:27:32 PM | P | CANC |
|
|
We installed a new 20 amp 120 volt circuit to a new receptacle for the above-the-range microwave.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell Inspection cancelled from web by: Dan Mitchell
|