Inspections for the day of: Friday, April 22, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00203 INSP-Final Inspection4/21/20054/22/20054/22/2005 5:14:12 PM FAIL
Replace fusible link and solder pendents in entry with QR as noted in plan review comment #10. Provide current inspection tag on riser. Install ceiling tile around pendent heads prior to final. Space head in laundry room for ordinary hazard req.
FIR05-00039 INSP-Sprinkler Rough-in/Hydro4/22/20054/22/20054/22/2005 3:18:11 PMPPART
Fire supply UG stub out good for cover, will require as-built for additional 90 okayed by Bill A. per Jim Danes.
BLD03-01644 FIRE-Final Inspection4/22/20054/22/20054/22/2005 12:02:21 PMAPASS
Fire life safety finaled.
BLD05-00484 FIRE-Final Inspection4/22/20054/22/20054/22/2005 11:58:30 AMPPASS
Fire life safety finaled.
FIR05-00107 INSP-Final Inspection4/21/20054/22/20054/22/2005 11:55:39 AMAPART
Overhead rough-in pass, need ceiling tile installed around pendent heads for final.
FIR05-00047 INSP-Final Inspection4/21/20054/22/20054/22/2005 11:53:29 AMAFAIL
Head overspaced in file and photocopy room. Provide fire caulk at penetration of line in riser room.
FIR04-00807 INSP-Final Inspection4/21/20054/22/20054/22/2005 11:50:31 AMAFAIL
Pipe size installed in mechanical room does not meet requirements of note #2 on review comments.
FIR04-00658 INSP-Final Inspection4/20/20054/22/20054/22/2005 9:26:04 AMAPART
Fire alarm 2nd floor pass inspection.
FIR04-00685 INSP-Alarm Testing4/22/20054/22/20054/22/2005 12:00:00 AMAPASS
Fire alarm finaled.