Inspections for the day of: Tuesday, April 22, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00595 INSP-Final Inspection4/21/20084/22/20084/23/2008 11:50:41 AMAPART
Fire phones at all locations tested satisfactory, need to add one phone jack at the fire pump room. Also noted missing work table and land line phone at the fire command center to be provided as discussed.
FIR08-00226 INSP-Final Inspection4/21/20084/22/20084/22/2008 4:06:09 PMPPASS
Fire alarm field testing passed, permit final okay.
BLD08-00428 FIRE-Final Inspection4/18/20084/22/20084/22/2008 4:04:59 PMPFAIL
Need to final project related fire sprinkler permit prior to life safety approval.
BLD08-00428 FIRE-Alarm Testing4/18/20084/22/20084/22/2008 4:04:07 PMPDONE
Duplicate inspection request.
FIR08-00118 INSP-Final Inspection4/21/20084/22/20084/22/2008 4:03:23 PMPPASS
Fire alarm work passed field inspection, permit finaled.
FIR06-00535 INSP-Final Inspection4/21/20084/22/20084/22/2008 1:11:44 PMPPASS
NFPA 72 record of completion forms accepted, fire alarm permit finaled.
BLD07-02809 FIRE-Final Inspection4/21/20084/22/20084/22/2008 10:52:05 AMANR
Items on issued correction notice are not yet completed for reinspection per contractor. Final rescheduled for late afternoon per conversation.
FIR08-00044 FIR-Aging Inspection4/22/20084/22/20084/22/2008 10:45:56 AM DONE
Work is not completed for inspection, construction underway.
BLD06-02150 FIRE-Final Inspection4/21/20084/22/20084/22/2008 10:43:04 AMADEFR
Wrong inspection type called in, was intended for a structural final. Noted no fire inspection signatures are required per project details, notified contact by phone to reschedule as discussed.
FIR07-00958 INSP-Final Inspection4/21/20084/22/20084/22/2008 8:24:49 AMAPASS
Noted defficient items verified for completion, fire sprinkler permit work passed final inspection, permit finaled.
FIR08-00220 INSP-Final Inspection4/21/20084/22/20084/22/2008 8:21:35 AMAPASS
Fire sprinkler permit finaled, missing ceiling tile installed while on site.
FIR06-00535 INSP-Final Inspection4/21/20084/22/20084/21/2008 2:13:15 PMPCANC
Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner