FIR06-00594
| FIR-Aging Inspection | 4/22/2015 | 4/22/2015 | 4/27/2015 12:29:14 PM | | NR |
|
|
I spoke to Don and he is going to follow up.
|
FIR03-00397
| FIR-Aging Inspection | 4/22/2015 | 4/22/2015 | 4/23/2015 8:56:49 AM | | DEFR |
|
|
Contractor is out of business
|
FIR15-00243
| INSP-Final Inspection | 4/21/2015 | 4/22/2015 | 4/22/2015 3:47:42 PM | P | CANC |
|
|
CANCEL PER Don Kartchner
|
BLD15-01066
| FIRE-Final Inspection | 4/22/2015 | 4/22/2015 | 4/22/2015 3:29:15 PM | P | PASS |
|
|
Life safety passed
|
FIR14-00435
| INSP-Final Inspection | 4/20/2015 | 4/22/2015 | 4/22/2015 3:26:36 PM | P | FAIL |
|
|
All items tested ok except the fire sprinkler flow switches due to incorrect orfice and outside alarm bell being installed in the wrong location. Will also need the document box and knox box.
|
FIR13-00612
| INSP-Final Inspection | 4/20/2015 | 4/22/2015 | 4/22/2015 3:24:45 PM | P | FAIL |
|
|
Inspected tamper switch interconnection with the FACP but could not do much else do to the painter starting to paint (multiple heads have been replaced due to paint), correct orfice not installed on the inspectors test and the outside alarm bell has been installed at the riser room not at the FDC which is on the other side of the building. Also I'm going to contact the fire dept about the FDC placement due to a fence being installed between the FDC and the street.
|
FIR15-00038
| INSP-Sprinkler Rough-in/Hydro | 4/22/2015 | 4/22/2015 | 4/22/2015 2:36:43 PM | P | PART |
|
|
Overhead hydro test passed. Rough-in passed for the most part. Missing two longitudinal braces on the 1 1/2" main and two branch line restraints under the mezzanine. Need updated/approved plans showing the pipe sizing and pipe routing changes under the mezzanine prior to a final sign off.
|
BLD14-02855
| FIRE-Final Inspection | 4/21/2015 | 4/22/2015 | 4/22/2015 9:48:30 AM | A | PASS |
|
|
Life safety passed by Forrest on 4/3/15
|
BLD15-00283
| FIRE-Final Inspection | 4/21/2015 | 4/22/2015 | 4/22/2015 9:42:23 AM | A | PASS |
|
|
Life safety passed
|
FIR14-00708
| INSP-Sprinkler Rough-in/Hydro | 4/22/2015 | 4/22/2015 | 4/22/2015 9:19:49 AM | P | CANC |
|
|
Bldg G 1st and 2nd floor RTC Please call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|
BLD14-01410
| FIRE-Final Inspection | 4/21/2015 | 4/22/2015 | 4/22/2015 7:43:20 AM | A | PASS |
|
|
Life safety passed
|
FIR15-00125
| INSP-Final Inspection | 4/20/2015 | 4/22/2015 | 4/21/2015 8:13:00 AM | P | CANC |
|
|
Robert is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|