FIR15-00329
| INSP-Sprinkler Rough-in | 4/22/2016 | 4/22/2016 | 4/22/2016 3:53:34 PM | P | PASS |
|
|
North post indicator valve relocated to line up with landscaping, Rough to cover inspection for relocation/thrust blocks complete, approved for cover.
|
FIR15-00770
| INSP-Sprinkler Rough-in | 4/22/2016 | 4/22/2016 | 4/22/2016 12:02:30 PM | P | PASS |
|
|
Rough to cover inspection complete, tenting inspection complete, all overhead fire sprinkler piping approved for cover.
|
FIR15-00770
| INSP-Conference | 4/22/2016 | 4/22/2016 | 4/22/2016 12:00:28 PM | P | CANC |
|
|
Inspection request for rough to cover, not a conference. This request cancelled and a rough to cover request will be generated.
|
FIR16-00038
| INSP-Sprinkler Rough-in | 4/21/2016 | 4/22/2016 | 4/22/2016 11:10:00 AM | A | PASS |
|
|
Rough to cover inspection complete, all area's in scope of work approved for cover.
|
BLD15-02470
| FIRE-Final Inspection | 4/21/2016 | 4/22/2016 | 4/22/2016 10:50:00 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with curent inspection tags. Signage for fire sprinkler riser room to be installed before final building inspection. Final life fire safety inspection passed/complete.
|
FIR16-00086
| INSP-Final Inspection | 4/19/2016 | 4/22/2016 | 4/22/2016 9:52:29 AM | A | PART |
|
|
Partial final inspection of clean agent alarm panel/clean agent release complete. All devices associated with clean agent fire alarms/tank activation tested, all devices that were tested passed inspection. Clean agent fire panel is not connected to the buildings main fire alarm system, clean agent fire panel needs to be monitored by the buildings main fire alarm panel (any modifications to the buildings fire alarm system will require a seperate FIR permit issued before work can be performed). A follow up inspection will need to be scheduled after interface between clean agent and main fire panel are complete. Once the panel interface is complete and inspected this FIR permit can be completed.
|
BLD16-00028
| FIRE-Final Inspection | 4/21/2016 | 4/22/2016 | 4/22/2016 8:20:31 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher in place in office area, fire extinguisher will be placed in discussed location in warehouse area. Final life fire safety inspection passed/complete.
|