Inspections for the day of: Monday, April 22, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02369 Electrical Rough-In4/22/20194/22/20194/22/2019 3:29:52 PMPPART
Two exterior canopies and 5th Floor elevator lobby. Call Joey C. prior to arrival. If no answer, call Ben M. at ###-####. Phone #: ###-#### Inspection requested via web by Scott Campbell
300.11- Ceiling support system shall not support raceways or cable unless manufacturers instructions state system has been tested for support of such cables and raceways. Contractor is checking instructions.
Level 5 elevator lobby wall and south lobby hardlid rough in ok cover
ELE19-00107 Final4/19/20194/22/20194/22/2019 2:22:37 PMPFAIL
Please call Kent ###-#### with at least a 30 minute heads up to meet you. If you have any questions please feel free to contact Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 210.12- All Master bedroom outlets shall have AFCI protection. Panel in basement.
ELE18-04393 Final4/19/20194/22/20194/22/2019 1:46:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE19-00934 Electrical Rough-In4/19/20194/22/20194/22/2019 12:57:18 PMAFAIL
Ceiling rough-in Phone #: ###-#### Inspection requested via web by Steven Ragan
300.11- Cables and raceways shall not be supported by the ceiling assembly including ceiling suport wires. Cables moved from short support wires to ceiling support wires.
ELE19-01440 Electrical Rough-In4/22/20194/22/20194/22/2019 11:19:22 AMPCANC
Along Fairview underground Phone #: ###-#### >> Inspection requested via web by Jason Wicks Inspection cancelled from web by: Jason Wicks
ELE19-01386 Temporary Service4/22/20194/22/20194/22/2019 10:27:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE19-01426 Rough-In Permanent Service4/19/20194/22/20194/22/2019 9:58:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman
Rough in ok cover p/s u/g n ok
ELE19-01194 Final4/19/20194/22/20194/22/2019 9:44:10 AMAFAIL
Code for door lock box 5584. Phone #: ###-#### Inspection requested via web by Nick Avery 210.11- Bathroom receptacle outlets shall be fed by a dedicated 20 amp circuit as noted to previous contractor on 6-15-18.
210.52- A receptacle outlet shall be located with in 24" of left side of kitchen sink.
314.20- Where boxes are mounted in non combustible wall cover and are recessed more than 1/4" a spark ring shall be installed.
408.4- Circuit directory shall accurately describe circuitd function.
*Dining light hanging on wires, several lights not working.
ELE19-01422 Rough-In Permanent Service4/19/20194/22/20194/22/2019 8:44:29 AMAPASS
this is for the garage. not the house Phone #: ###-#### Inspection requested via web by Paula Gratiot
Service on house moving to garage, 200 amp on shop with sub-feed to house.
Shop rough in ok cover p/s o/h n ok