ELE19-04182
| Electrical Rough-In | 4/22/2020 | 4/22/2020 | 4/22/2020 2:58:18 PM | P | FAIL |
|
|
Roughed this in back in I believe November then they had issues with the plans but I think everything is good to go now. Call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe 110.12(B)- Equipment shall not be damaged. Replace or repair MC where outer cover seperated in 1/2 wall office. 300.4- Where MC is run thru bored holes that do not maintain 1 1/4" from framing surface cable shall be protected from damage. N.E. office. 348.30- Flex and EMT shall be supported and secured so not hanging below ceiling trusses. City approved set pf prints shall be on site prior to inspection.
|
ELE19-03829
| Electrical Rough-In | 4/21/2020 | 4/22/2020 | 4/22/2020 1:24:23 PM | P | PASS |
|
|
Electrical rough-in inspection for the lightning protection ground grounding on the 9th floor. Contact electrician Shawn Evins with any questions. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Listing on compnents confirmed. Rough in ok cover.
|
ELE19-04799
| Conference | 4/21/2020 | 4/22/2020 | 4/22/2020 10:58:07 AM | A | PASS |
|
|
Can be teleconference or video conference to discuss construction, installation, and grounding of pool and structure at the 5th floor amenity deck. Phone #: ###-#### Inspection requested via web by Jason Parke Met Jason on site and discussed bonding of pool located on level 5. As per 680.26 bonding of shell, ladders, and perimeter however perimeter is elevated pavers. An equipotential bond will need to be installed under pavers on top of stands to bond potential wet perimeter surface. When in dought we will be bonding any and all areas needed.
|
ELE20-00739
| Electrical Rough-In | 4/21/2020 | 4/22/2020 | 4/22/2020 10:12:57 AM | A | NR |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Unable to locate a 24' x 3'2" sign for New York Life on exterior of building. Called contact, said they would have to reschedule due to not able to get trucks where needed because of dumpsters.
|
ELE20-01101
| Electrical Rough-In | 4/20/2020 | 4/22/2020 | 4/22/2020 9:49:29 AM | A | PASS |
|
|
Wall rough in. Phone #: ###-#### Inspection requested via web by Deb Morton Asked to provide GFCI temp power as per 590.6. City approved set of prints on site. Walls and hardlids rough in ok cover.
|