ELE07-00046
| Electrical Rough-In | 4/23/2007 | 4/23/2007 | 4/23/2007 4:14:30 PM | P | NR |
|
|
Above ceiling inspection please. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw 300.11 wires for support of cables , high and low voltage, 400.8 no cords above ceiling time clock above panels
|
ELE07-01217
| Electrical Rough-In | 4/23/2007 | 4/23/2007 | 4/23/2007 3:37:29 PM | P | PART |
|
|
bruce - panel insp. ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith sub panels ok
|
ELE06-04726
| Final | 4/23/2007 | 4/23/2007 | 4/23/2007 3:02:26 PM | P | PASS |
|
|
Final inspection please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok card signed
|
ELE07-01430
| Electrical Rough-In | 4/23/2007 | 4/23/2007 | 4/23/2007 2:30:21 PM | P | PASS |
|
|
###-#### dustin ok
|
ELE07-01380
| Final | 4/23/2007 | 4/23/2007 | 4/23/2007 2:04:48 PM | P | PASS |
|
|
Electrician - Tony Norton ###-#### Resident - John and Pam Wall ###-#### Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer
|
ELE07-00993
| Final | 4/23/2007 | 4/23/2007 | 4/23/2007 1:32:50 PM | P | FAIL |
|
|
david; Phone #: ###-#### Internet Inspection Request from: Victoria Beall could not locate, called no response, shall be called in for t/s not final
|
ELE07-00639
| Final | 4/20/2007 | 4/23/2007 | 4/23/2007 12:52:36 PM | P | PASS |
|
|
Call Bobby Langer ###-#### Final inspection Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok card signed
|
ELE07-00639
| Electrical Rough-In | 4/23/2007 | 4/23/2007 | 4/23/2007 12:52:17 PM | P | PASS |
|
|
Call Bobby Langer ###-#### Final inspection Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ceilings ok
|
ELE07-01406
| Final | 4/20/2007 | 4/23/2007 | 4/23/2007 10:14:01 AM | A | FAIL |
|
|
circuit for water heater in basement, upgrade service. Thank you. Kim Furhman should be home, ###-#### Phone #: ###-#### x0000 Internet Inspection Request from: BRIAN KEITH corr. fee due, called 250.104 shall bond around anything that isolates metal piping, 250.24 all grds and bonds shall be at main p/s not sub panels , isolate grds and neutrals at sub pnaels, remove spliced grd wire at subpanel, BCC no violations retained , wiring for hot tub shall meet NEC 680, connectors for all cables old subpanel garage, circuit directory be specific, 334.15 protect new wiring in basement, 300.4 nail plates and 11/4"
|
ELE07-01077
| Final | 4/20/2007 | 4/23/2007 | 4/23/2007 8:41:42 AM | A | PASS |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok card signed
|
ELE07-01077
| Electrical Rough-In | 4/23/2007 | 4/23/2007 | 4/23/2007 8:41:31 AM | A | PASS |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ceiling ok
|
ELE07-01393
| Electrical Rough-In | 4/20/2007 | 4/23/2007 | 4/23/2007 12:00:00 AM | A | CANC |
|
|
Craig; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
|