Inspections for the day of: Thursday, April 23, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Strole
TitlePLM/MEC-INSPECTOR
Phone #794-7913
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC08-00698 Random Inspection4/23/20094/23/20094/23/2009 4:54:07 PMPFAIL
left verbal correction with rp to clean all concrete spoils, dirt & debris off all hard surfaces & post esc sign by 4-24-09. will reinspect 4-27-09 am.
ESC08-00179 BMP Violation4/22/20094/23/20094/23/2009 2:37:43 PMPPASS
2:30 pm reinspection-all corrections complete, site looks good.
PLM08-01619 Other4/22/20094/23/20094/23/2009 1:15:27 PMAPART
10:00 am walk thru with water perveyor bill thomson-need to install dbce on water supply, need to install approved backflow device on lawn sprinkler system, need to install pvb on 3 eyewash stations, need to install rpba on soap dispensor at mop sink or change out to unit with an airgap, label boiler make up water non-potable, provide thermal expantion & have all backflow devices tested & certified.
ESC06-01327 Site Final4/23/20094/23/20094/23/2009 10:54:18 AMAPASS
ESC04-00435 Site Final4/23/20094/23/20094/23/2009 9:45:30 AMAPASS
ESC08-00519 Site Final4/23/20094/23/20094/23/2009 9:23:58 AMAPASS
ESC08-00127 Site Final4/23/20094/23/20094/23/2009 9:23:36 AMAPASS
MIS09-00048 PLM-Conference4/22/20094/23/20094/23/2009 8:31:45 AMADONE
this was to sign civil penalty notice.