Inspections for the day of: Monday, April 23, 2012.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00034 INSP-Final Inspection4/20/20124/23/20124/23/2012 5:24:13 PMAPART
Begin 24 hr. test of the new dry system at 10:30 AM @41.5psig.
FIR11-00689 INSP-Sprinkler Rough-in4/19/20124/23/20124/23/2012 5:20:52 PMPNR
Preliminary inspection for overhead work at system 9 including partial install of 6" and 4" mains and 1 1/2" branchlines only. Upright heads, seismic bracing, tailbacks, 4" grid main, coverage at stairways and comm rooms are incomplete at this time.
FIR11-00659 INSP-Final Inspection4/23/20124/23/20124/23/2012 5:12:33 PMPPASS
FIR12-00179 INSP-Final Inspection4/23/20124/23/20124/23/2012 5:10:19 PMPPASS
Fire sprinkler work passed inspection, permit final approved.
FIR11-00575 INSP-Final Inspection4/23/20124/23/20124/23/2012 5:09:04 PMAPART
Operational test of the fire curtain and acceptance testing per NFPA 80 completed. Re-inspection passed.
FIR12-00166 INSP-Final Inspection4/23/20124/23/20124/23/2012 4:59:45 PMAPASS
Scope of fire alarm work passed inspection. Permit finaled.