Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00792 FIRE-Final Inspection4/20/20124/23/20124/23/2012 3:37:30 PMPFAIL
Provide racking permit for the racks that exceed 8'-0" in height. Storage exceeding 12'-0" in height required verification that the sprinkler system is adewuately designed for the stored commodity. This could require high pile storage permit. Provide access to verify annual inspection for fire sprinkler riser and functioning fire alarm system.
FIR12-00191 INSP-Final Inspection4/19/20124/23/20124/23/2012 2:34:33 PMAPASS
Permit finaled
FIR12-00161 INSP-Sprinkler Rough-in/Hydro4/20/20124/23/20124/23/2012 2:29:56 PMAPASS
The overhead hydro test for the pendant sprinkler piping has passed. The standpipe piping has not been hydro tested yet. The east wing corridor sprinkler piping can be covered.