BLD12-00792
| FIRE-Final Inspection | 4/20/2012 | 4/23/2012 | 4/23/2012 3:37:30 PM | P | FAIL |
|
|
Provide racking permit for the racks that exceed 8'-0" in height. Storage exceeding 12'-0" in height required verification that the sprinkler system is adewuately designed for the stored commodity. This could require high pile storage permit. Provide access to verify annual inspection for fire sprinkler riser and functioning fire alarm system.
|
FIR12-00191
| INSP-Final Inspection | 4/19/2012 | 4/23/2012 | 4/23/2012 2:34:33 PM | A | PASS |
|
|
Permit finaled
|
FIR12-00161
| INSP-Sprinkler Rough-in/Hydro | 4/20/2012 | 4/23/2012 | 4/23/2012 2:29:56 PM | A | PASS |
|
|
The overhead hydro test for the pendant sprinkler piping has passed. The standpipe piping has not been hydro tested yet. The east wing corridor sprinkler piping can be covered.
|