BLD12-03138
| FIRE-Final Inspection | 4/23/2013 | 4/23/2013 | 4/23/2013 4:56:47 PM | P | PASS |
|
|
Fire life safety final approved.
|
FIR12-00108
| INSP-Sprinkler Rough-in | 4/22/2013 | 4/23/2013 | 4/23/2013 4:55:25 PM | A | FAIL |
|
|
Completed inspection for the remainder of work at the 3rd floor- vestibule at stair #2 now has a drop ceiling, coverge at electrical room adjacent to stair #3 is overspaced, comm room is not finished, five light fixture obstructions at the storage room. System 2 remote calc area #3 does not match field installation- pipe sizing, head type/layout, branchlines and room area are different.
|
FIR13-00103
| INSP-Sprinkler Rough-in | 4/22/2013 | 4/23/2013 | 4/23/2013 4:43:56 PM | A | PART |
|
|
Overhead work at the grid ceilings is approved for cover. Need to check coverage opposite new wall NW corner- added upright appears missing.
|
FIR13-00175
| INSP-Sprinkler Rough-in | 4/23/2013 | 4/23/2013 | 4/23/2013 4:36:22 PM | A | PART |
|
|
UG fire supply line IBR is approved for bury.
|
BLD13-00674
| FIRE-Final Inspection | 4/17/2013 | 4/23/2013 | 4/23/2013 4:34:52 PM | A | PASS |
|
|
Noted correction items have been finished. Life safety passed.
|
BLD13-00620
| FIRE-Final Inspection | 4/22/2013 | 4/23/2013 | 4/23/2013 4:32:10 PM | A | PASS |
|
|
Correction items verified for completion. Fire life safety passed.
|
FIR13-00139
| INSP-Sprinkler Rough-in | 4/22/2013 | 4/23/2013 | 4/23/2013 4:28:31 PM | A | PART |
|
|
Overhead fire sprinkler modifications are approved for cover at the drop ceilings.
|
FIR13-00142
| INSP-Sprinkler Rough-in | 4/22/2013 | 4/23/2013 | 4/23/2013 4:18:37 PM | A | PART |
|
|
Overhead rough-in completed. Cover approval pending verification of cold cavity protection when installed. Missing coverage below the upper stair landing, riser is not yet built, DP at the garage are on order.
|