BLD14-00496
| FIRE-Final Inspection | 4/23/2014 | 4/23/2014 | 4/23/2014 4:39:19 PM | P | PASS |
|
|
Shell only per scope of permit.
|
BLD14-00883
| FIRE-Conference | 4/22/2014 | 4/23/2014 | 4/23/2014 3:47:14 PM | P | DONE |
|
|
On site conference regarding remodel work and modifications needed to maintain fire sprinkler coverage. Also discussed additional exit signage and emergency lighting (annotated locations on plans), door hardware, fire extinguisher placement, etc.
|
FIR14-00073
| INSP-Final Inspection | 4/21/2014 | 4/23/2014 | 4/23/2014 3:12:34 PM | P | PASS |
|
|
Fire alarm work passed site inspection and acceptance testing. Permit finaled.
|
FIR14-00188
| INSP-Sprinkler Rough-in | 4/23/2014 | 4/23/2014 | 4/23/2014 3:11:04 PM | P | PART |
|
|
Overhead work at the sheetrock soffits approved for cover. Verified upright coverage throughout.
|
FIR14-00177
| INSP-Sprinkler Rough-in | 4/17/2014 | 4/23/2014 | 4/23/2014 11:18:30 AM | A | PART |
|
|
UG fire supply line ductile riser piece and 6" C-900 stub out to a point 8' beyond the stem wall okay for bury.
|
BLD13-02639
| FIRE-Final Inspection | 4/22/2014 | 4/23/2014 | 4/23/2014 10:10:17 AM | A | FAIL |
|
|
HVAC unit did not shut down upon smoke detection. Verified new annunciator and repaired exit signs and emergency lights. Need to remove non-applicable address numbers adjacent to the main entry exit doors.
|
BLD14-00305
| FIRE-Final Inspection | 4/22/2014 | 4/23/2014 | 4/23/2014 9:36:42 AM | A | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
FIR14-00180
| INSP-Final Inspection | 4/22/2014 | 4/23/2014 | 4/23/2014 9:35:57 AM | A | PASS |
|
|
Fire sprinkler work passed final walkthrough. Permit finaled.
|