Inspections for the day of: Wednesday, April 23, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-00496 FIRE-Final Inspection4/23/20144/23/20144/23/2014 4:39:19 PMPPASS
Shell only per scope of permit.
BLD14-00883 FIRE-Conference4/22/20144/23/20144/23/2014 3:47:14 PMPDONE
On site conference regarding remodel work and modifications needed to maintain fire sprinkler coverage. Also discussed additional exit signage and emergency lighting (annotated locations on plans), door hardware, fire extinguisher placement, etc.
FIR14-00073 INSP-Final Inspection4/21/20144/23/20144/23/2014 3:12:34 PMPPASS
Fire alarm work passed site inspection and acceptance testing. Permit finaled.
FIR14-00188 INSP-Sprinkler Rough-in4/23/20144/23/20144/23/2014 3:11:04 PMPPART
Overhead work at the sheetrock soffits approved for cover. Verified upright coverage throughout.
FIR14-00177 INSP-Sprinkler Rough-in4/17/20144/23/20144/23/2014 11:18:30 AMAPART
UG fire supply line ductile riser piece and 6" C-900 stub out to a point 8' beyond the stem wall okay for bury.
BLD13-02639 FIRE-Final Inspection4/22/20144/23/20144/23/2014 10:10:17 AMAFAIL
HVAC unit did not shut down upon smoke detection. Verified new annunciator and repaired exit signs and emergency lights. Need to remove non-applicable address numbers adjacent to the main entry exit doors.
BLD14-00305 FIRE-Final Inspection4/22/20144/23/20144/23/2014 9:36:42 AMAPASS
Fire life safety inspection completed satisfactory.
FIR14-00180 INSP-Final Inspection4/22/20144/23/20144/23/2014 9:35:57 AMAPASS
Fire sprinkler work passed final walkthrough. Permit finaled.