Inspections for the day of: Thursday, April 23, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00529 INSP-Sprinkler Rough-in4/20/20154/23/20154/24/2015 2:13:24 PMAPART
Hydrostatic test on all four risers in new warehouse satisfactory completed.
FIR39-00005 INSP-Sprinkler Rough-in/Hydro4/23/20154/23/20154/24/2015 8:23:57 AMAPASS
BLD14-02599 FIRE-Final Inspection4/23/20154/23/20154/23/2015 3:13:50 PMPPASS
Fire Life Safety pass. One exit sign at interior entrance to new room to be repaired (batteries) prior to final bldg inspection.
FIR15-00108 INSP-Final Inspection4/22/20154/23/20154/23/2015 2:45:05 PMPFAIL
Two notification devices need to be adjusted to meet code. Three in duct spot detectors and duct detectors were tested, verified acceptable damper closure and fan shut down. Notification not tested.
FIR14-00815 INSP-Sprinkler Rough-in/Hydro4/22/20154/23/20154/23/2015 11:31:35 AMAPART
24 hr air test for dry systems 1 and 2 completed satisfactory. End pressures recorded, system one 40.5 psig, system two 43 psig. Completed rough-in for dry system 3 on fourth floor. Correction items are as follows straighten on two heads in rm 424, and one head each in rms 426 and 423. RM 420 has two obstructed heads to be relocated and 2 missing hangars. Rm 414 has a head located under vent to be moved to side. Previous C/N items were not able to be corrected due to pressure system, to be verified at next inspection.
BLD15-00395 FIRE-Final Inspection4/22/20154/23/20154/23/2015 11:26:54 AMAPASS
Life Safety pass. Verified all extinguisher and hood suppression system are current on annual inspections.
BLD14-00936 FIRE-Final Inspection4/22/20154/23/20154/23/2015 9:46:27 AMAPASS
Life Safety Pass. Verified new bathroom hardware exceptable.