Inspections for the day of: Monday, April 23, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01451 Electrical Rough-In4/23/20184/23/20184/24/2018 9:10:39 AMPPASS
Ron-pool bonding Phone #: ###-####...4 corners, cover, and 4 lights
ELE18-01154 Conference4/23/20184/23/20184/23/2018 3:40:42 PMPPASS
Tom Phone #: ###-####...adding outlets off existing circuit in shed...pamphlet given...homeowner very capable to do work
ELE18-01528 Rough-In Permanent Service4/23/20184/23/20184/23/2018 2:39:00 PMPPASS
Phone #: ###-#### Inspection requested via web by ron spen cer...rough ok to cover...p/s u/g new ok
ELE18-01528 Rough-In Permanent Service4/23/20184/23/20184/23/2018 2:38:21 PMPCANC
Phone #: ###-#### Inspection requested via web by ron spen cer...scheduled twice
ELE18-01522 Electrical Rough-In4/22/20184/23/20184/23/2018 1:46:35 PMPPASS
Phone #: ###-#### Inspection requested via web by Andy Derrick...3 new circuits for new upstairs entertainment room and can lighting downstairs of existing circuit...rough ok to cover
ELE18-01290 Electrical Rough-In4/23/20184/23/20184/23/2018 1:27:07 PMPPASS
Brian Prussia Phone #: ###-####...UL listed equipment verified
ELE18-01495 Final4/22/20184/23/20184/23/2018 12:10:52 PMPPASS
panel change final Phone #: ###-#### Inspection requested via web by kyle carson..ok to final
ELE18-00973 Final4/22/20184/23/20184/23/2018 10:03:49 AMAPASS
All panels complete side garage man door should be open! Any questions please give me a call! Thx. Steve, BPL Phone #: ###-#### Inspection requested via web by Steven Meredith...ok to final
ELE18-01456 Final4/20/20184/23/20184/23/2018 9:15:19 AMAFAIL
Steve Hook is contact ###-#### Phone #: ###-#### Inspection requested via web by Debby Pierce...
1..flexible cords and cables shall be protected from accidental damage...590.4(H)
2..all temporary installations shall have GFCI protection...240V breakers...590.6
ELE18-01525 Final4/22/20184/23/20184/23/2018 8:46:59 AMACANC
Manufactured home new hook up from existing pedestal. Phone #: ###-#### Inspection requested via web by kyle carson...unable to final at this time...need to schedule once power connected
ELE18-01525 Permanent Service4/23/20184/23/20184/23/2018 8:46:13 AMAPASS
Manufactured home new hook up from existing pedestal. Phone #: ###-#### Inspection requested via web by kyle carson...p/s u/g new ok
ELE13-00731 ELE-Aging Inspection4/23/20184/23/20184/23/2018 8:40:15 AM DONE
owner not compliant with needed correction