ELE19-01437
| Final | 4/22/2019 | 4/23/2019 | 4/23/2019 1:49:00 PM | P | FAIL |
|
|
Please call Dave at ###-#### before heading over. Thanks Phone #: ###-#### Inspection requested via web by Steven Ragan 422.12- Central heating equipment shall be supplied by an individual branch circuit. Set junction box where furnace wire stubbed and tapped off to receptacle for tankless system.
|
ELE19-01208
| Electrical Rough-In | 4/23/2019 | 4/23/2019 | 4/23/2019 1:16:12 PM | P | PASS |
|
|
Underground and bonding for swimming pool. Access granted at South East corner of residence where trenching was done Phone #: ###-#### Inspection requested via web by Lars Johnson Under ground from equipment to pool and spa. Bonds for all 4 corners, each end of pool cover, and from shell to equipment rough in ok cover.
|
ELE19-01392
| Temporary Service | 4/23/2019 | 4/23/2019 | 4/23/2019 11:22:32 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 110.14- Lugs at top of panel loose and grounding electrode conductor at transformer loose.
|
ELE19-01393
| Temporary Service | 4/23/2019 | 4/23/2019 | 4/23/2019 11:10:52 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
|
ELE19-00530
| Final | 4/23/2019 | 4/23/2019 | 4/23/2019 10:48:01 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
|
ELE19-00531
| Final | 4/23/2019 | 4/23/2019 | 4/23/2019 10:47:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
|
ELE19-01453
| Electrical Rough-In | 4/22/2019 | 4/23/2019 | 4/23/2019 10:06:33 AM | A | PASS |
|
|
coming from emmett to unlock.will try to be there by 8 if not shortly after thanks Phone #: ###-#### Inspection requested via web by brian morrow Kitchen bar wall and laundry receptacles moved rough in ok cover
|
ELE19-01430
| Electrical Rough-In | 4/22/2019 | 4/23/2019 | 4/23/2019 9:50:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake 2nd ELE for adjacent TI, will address when called. Discussed a 378 sq.ft. conference room requiring 2 floor receptacles. Contact explained print to be resubmitted to change use of room to other than conference room. Wall rough in ok cover
|
ELE19-00659
| Electrical Rough-In | 4/22/2019 | 4/23/2019 | 4/23/2019 9:25:24 AM | A | PASS |
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden Conference room walls and hardlid rough in ok cover
|
ELE19-00531
| Rough-In Permanent Service | 4/23/2019 | 4/23/2019 | 4/23/2019 7:25:55 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson Inspection cancelled from web by: Therrin Robertson
|