MEC20-01560
| Final | 4/22/2020 | 4/23/2020 | 4/23/2020 3:41:17 PM | P | PART |
|
|
Need to have inspection at the end of the day, near 4 pm. If I can not have that then it will need to reschedule. thank you Phone #: ###-#### Inspection requested via web by Doug LaMott- furnace a/c coil co ok- need locking caps on a/c service ports and uv protection on lineset outside at a/c- send pic for reinspect
|
MEC20-01594
| Final | 4/22/2020 | 4/23/2020 | 4/23/2020 3:01:03 PM | P | PASS |
|
|
Please call Paul prior to arrival to ensure ready- ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- furnace a/c coil co locking caps ok
|
MEC20-01596
| Rough-in | 4/23/2020 | 4/23/2020 | 4/23/2020 2:27:41 PM | P | PASS |
|
|
Tony Phone #: ###-####- R/I ok
|
MEC20-01409
| Rough-in | 4/23/2020 | 4/23/2020 | 4/23/2020 1:09:07 PM | P | PASS |
|
|
Building 10 for cover 6 units - please contact shawn @ 2089602011 Phone #: ###-#### Inspection requested via web by Amanda Casper- R/I on units M 201 203 301 302 303 and 304 seal on duct ok- ok to cover
|
MEC19-04813
| Final | 4/22/2020 | 4/23/2020 | 4/23/2020 10:42:06 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brent Lacy- gas piping final ok
|
MEC20-01576
| Rough-in | 4/22/2020 | 4/23/2020 | 4/23/2020 8:56:48 AM | A | FAIL |
|
|
Ready for rough in inspection and gas line pressure and pvc flu pressure test. House open Phone #: ###-#### Inspection requested via web by Russ Curtis 1- dryer vent can not run in 2x4 wall needs firred out or reroute in crawl 2- need 10 mil tape on gas line penetration thru wall at meter location 3- line set needs installed on R/I 4- front bedroom missing 1 supply per approved man J onsite
left correction notice at furnace
|
MEC20-01576
| Pressure Test | 4/23/2020 | 4/23/2020 | 4/23/2020 8:53:07 AM | A | PASS |
|
|
Ready for rough in inspection and gas line pressure and pvc flu pressure test. House open Phone #: ###-#### Inspection requested via web by Russ Curtis- 20lb gas pass tagged meter location- 5lb flue x 2 ok
|
MEC19-00655
| Mec-Aging Inspection | 4/23/2020 | 4/23/2020 | 4/23/2020 8:09:28 AM | | FAIL |
|
|
called contractor and left message no answer- permit has not been active since pressure test in July of 2019- schedule inspection- permit will expire next aging if no activity
|
MEC19-04006
| Mec-Aging Inspection | 4/23/2020 | 4/23/2020 | 4/23/2020 8:06:03 AM | | CANC |
|
|
WIP- still needs address addressed
|