Inspections for the day of: Thursday, April 23, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-01560 Final4/22/20204/23/20204/23/2020 3:41:17 PMPPART
Need to have inspection at the end of the day, near 4 pm. If I can not have that then it will need to reschedule. thank you Phone #: ###-#### Inspection requested via web by Doug LaMott- furnace a/c coil co ok- need locking caps on a/c service ports and uv protection on lineset outside at a/c- send pic for reinspect
MEC20-01594 Final4/22/20204/23/20204/23/2020 3:01:03 PMPPASS
Please call Paul prior to arrival to ensure ready- ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- furnace a/c coil co locking caps ok
MEC20-01596 Rough-in4/23/20204/23/20204/23/2020 2:27:41 PMPPASS
Tony Phone #: ###-####- R/I ok
MEC20-01409 Rough-in4/23/20204/23/20204/23/2020 1:09:07 PMPPASS
Building 10 for cover 6 units - please contact shawn @ 2089602011 Phone #: ###-#### Inspection requested via web by Amanda Casper- R/I on units M 201 203 301 302 303 and 304 seal on duct ok- ok to cover
MEC19-04813 Final4/22/20204/23/20204/23/2020 10:42:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Brent Lacy- gas piping final ok
MEC20-01576 Rough-in4/22/20204/23/20204/23/2020 8:56:48 AMAFAIL
Ready for rough in inspection and gas line pressure and pvc flu pressure test. House open Phone #: ###-#### Inspection requested via web by Russ Curtis
1- dryer vent can not run in 2x4 wall needs firred out or reroute in crawl
2- need 10 mil tape on gas line penetration thru wall at meter location
3- line set needs installed on R/I
4- front bedroom missing 1 supply per approved man J onsite

left correction notice at furnace
MEC20-01576 Pressure Test4/23/20204/23/20204/23/2020 8:53:07 AMAPASS
Ready for rough in inspection and gas line pressure and pvc flu pressure test. House open Phone #: ###-#### Inspection requested via web by Russ Curtis- 20lb gas pass tagged meter location- 5lb flue x 2 ok
MEC19-00655 Mec-Aging Inspection4/23/20204/23/20204/23/2020 8:09:28 AM FAIL
called contractor and left message no answer- permit has not been active since pressure test in July of 2019- schedule inspection- permit will expire next aging if no activity
MEC19-04006 Mec-Aging Inspection4/23/20204/23/20204/23/2020 8:06:03 AM CANC
WIP- still needs address addressed