Inspections for the day of: Wednesday, April 24, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-00008 Electrical Rough-In4/23/20024/24/20024/24/2002 12:00:00 AMAFAIL
r/i- bobby- ###-####-- grid ceiling do not cover posted called some open j boxes and need to clip fixtures to grid 4/24/2002 11:52:00 AM
ELE02-00664 Final4/23/20024/24/20024/24/2002 12:00:00 AMAPASS
###-#### miller ok 4/24/2002 11:09:04 AM
ELE02-01188 Permanent Service4/23/20024/24/20024/24/2002 12:00:00 AMAFAIL
gary- ###-####--key in mailbox for front door
cor. posted called 314.19 surface box es open in back,250.148 all j boxes 314.15 replace old fuse box used as j box with raintight box BCC outlet spacing in bedroom shall meet intent of 210.52(A) N E bedrm only 4/24/2002 10:44:49 AM
ELE02-01188 Final4/23/20024/24/20024/24/2002 12:00:00 AMAFAIL
gary ###-#### fn--key in the mailbox for front door see p/s inspection request 4/24/2002 10:45:19 AM
ELE02-01166 Rough-In Permanent Service4/24/20024/24/20024/24/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 04/24/2002 at 06:12:21. Contact: ###-####. r/i ok

p/s u/g new ok 4/24/2002 1:02:29 PM
ELE02-01164 Rough-In Permanent Service4/24/20024/24/20024/24/2002 12:00:00 AMPPART
###-#### JERRY conference on will stop back later PM when p/s is ready 4/24/2002 3:29:06 PM
ELE01-02099 Final4/24/20024/24/20024/24/2002 12:00:00 AMPPASS
###-#### ok bld #25 section B 4/24/2002 4:51:17 PM
ELE02-01164 Permanent Service4/24/20024/24/20024/24/2002 12:00:00 AMPNR
job still not if he is ready 412 will do inspection 4/24/2002 5:20:40 PM