Inspections for the day of: Monday, April 24, 2006.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00696 Final4/24/20064/24/20064/24/2006 4:30:39 PMPPASS
Scheduled by a contractor via Hello! on 4/24/2006 at 7:55:48 AM. Contact: ###-####. corr done, ok to final
ELE05-04108 ELE-Aging Inspection4/24/20064/24/20064/24/2006 4:10:56 PM DONE
see final
ELE05-04108 Final4/24/20064/24/20064/24/2006 4:10:02 PMPPASS
freezer done by another contractor, ok to final
ELE06-01398 Temporary Service4/24/20064/24/20064/24/2006 3:58:31 PMPFAIL
###-#### - rick called contr, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be provided, 110.14(A) grounding electrode connection to terminal at rod shall ensure a thoroughly good connection, fee due
ELE06-01397 Temporary Service4/24/20064/24/20064/24/2006 3:45:04 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: William Zerfas called contr, left message, left corr notice, 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be provided, Note: pole shall be firmly set, fee due.
ELE06-01332 Rough-In Permanent Service4/21/20064/24/20064/24/2006 2:58:46 PMPPASS
Scheduled by a contractor via Hello! on 4/21/2006 at 2:38:45 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
ELE06-01395 Electrical Rough-In4/24/20064/24/20064/24/2006 2:31:17 PMPCANC
###-#### - spencer see rip, wrong inspection request
ELE06-01395 Rough-In Permanent Service4/24/20064/24/20064/24/2006 2:30:29 PMPPASS
###-#### - spencer called contr, left survey BCC all make-up shall be done and set box for range, ric ok, p/s u/g n ok
ELE06-00892 Electrical Rough-In4/24/20064/24/20064/24/2006 1:58:42 PMPPASS
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
ELE05-04279 Electrical Rough-In4/24/20064/24/20064/24/2006 1:15:40 PMPPASS
ron -use either gate & dogs are in locked in kennel ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ric ok
ELE06-00921 Conference4/23/20064/24/20064/24/2006 11:59:45 AMACANC
We request a conference to discuss the use of this office space and what the code requires,since there have been questions concerning the occupancy. We would request both Bob and Jim to be present sometime between 8:00am and 10:00am at your convenience.
Thank you
Koyama Inc.; Phone #: ###-#### Internet Inspection Request from: kendall bender see ri
ELE06-00921 Electrical Rough-In4/24/20064/24/20064/24/2006 11:39:33 AMAPASS
We request a conference to discuss the use of this office space and what the code requires,since there have been questions concerning the occupancy. We would request both Bob and Jim to be present sometime between 8:00am and 10:00am at your convenience.
Thank you
Koyama Inc.; Phone #: ###-#### Internet Inspection Request from: kendall bender called for conference, met with 324 and 370 and contr, then gave ri inspection, walls only ok to cover
ELE06-00892 Electrical Rough-In4/21/20064/24/20064/24/2006 10:38:09 AMAFAIL
bill; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, BCC all make-up shall be done, nec 210.52(D) each basin in batf shall have recpt within 3' of basin, 210.52(A) recpt spacing shall be within 12' along wall line in mbr, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 250.86 all metal boxes shall be grounded
ELE06-01313 Electrical Rough-In4/21/20064/24/20064/24/2006 10:31:41 AMAPASS
Scheduled by a contractor via Hello! on 4/21/2006 at 1:36:35 PM. Contact: ###-####. u/g ok to cover
ELE06-01369 Electrical Rough-In4/24/20064/24/20064/24/2006 9:41:45 AMAPASS
Please inspect remodel. journeyman will be onsitefor morining inspection after 8:00-*:30; Phone #: ###-#### Internet Inspection Request from: William Zerfas ric ok
ELE06-01381 Temporary Service4/21/20064/24/20064/24/2006 8:49:06 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty called contr, left corr notice, BCC job id shall be posted, address shall be posted, nec 312.5 abrasion protection shall be provided for conductors entering enclosure, 408.4 circuit directory shall be provided, fee due
ELE06-01352 Temporary Service4/22/20064/24/20064/24/2006 8:26:07 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr to wire recpt and abrasion prot for gec, t/s o/h n ok
ELE06-01367 Rough-In Permanent Service4/21/20064/24/20064/21/2006 3:42:34 PMPCANC
Scheduled by a contractor via Hello! on 4/21/2006 at 6:52:01 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Apr 21 2006 3:42PM.
ELE06-01367 Rough-In Permanent Service4/20/20064/24/20064/21/2006 6:53:07 AMACANC
Scheduled by a contractor via Hello! on 4/20/2006 at 2:19:32 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Apr 21 2006 6:53AM.