FIR05-00288
| FIR-Aging Inspection | 4/24/2006 | 4/24/2006 | 4/27/2006 12:47:04 PM | | PASS |
|
|
Work for the permitted demolition has been completed.
|
BLD05-02024
| FIRE-Final Inspection | 4/24/2006 | 4/24/2006 | 4/24/2006 4:46:18 PM | P | PASS |
|
|
Life safety finaled.
|
BLD05-02474
| FIRE-Final Inspection | 4/24/2006 | 4/24/2006 | 4/24/2006 4:44:45 PM | P | FAIL |
|
|
Pending sprinkler permit final request.
|
BLD05-02475
| FIRE-Final Inspection | 4/24/2006 | 4/24/2006 | 4/24/2006 4:43:42 PM | P | FAIL |
|
|
The project related sprinkler permit needs to be called for final.
|
BLD05-02476
| FIRE-Final Inspection | 4/24/2006 | 4/24/2006 | 4/24/2006 2:31:45 PM | P | FAIL |
|
|
The project related sprinkler permit must be finaled first.
|
FIR05-00594
| INSP-Final Inspection | 4/24/2006 | 4/24/2006 | 4/24/2006 2:02:19 PM | P | PART |
|
|
Need to remove "construction caps" at the pendent heads in the showers on the 1st floor, install missing escutcheons at some locations.
|
FIR05-00349
| INSP-Final Inspection | 4/24/2006 | 4/24/2006 | 4/24/2006 1:46:24 PM | P | PASS |
|
|
Flush and hydro test completed under inspection requests for the project related overhead system permit number. UG fire supply line permit finaled.
|
FIR06-00053
| INSP-Final Inspection | 4/21/2006 | 4/24/2006 | 4/24/2006 1:43:28 PM | A | PASS |
|
|
Fire sprinkler work passed final inspection.
|
FIR05-00449
| INSP-Alarm Testing | 4/23/2006 | 4/24/2006 | 4/24/2006 12:16:11 PM | A | PASS |
|
|
Fire alarm work passed final inspection, permit finaled.
|
BLD04-02348
| FIRE-Final Inspection | 4/22/2006 | 4/24/2006 | 4/24/2006 12:10:46 PM | A | FAIL |
|
|
Project is not ready for life safety final at this point due to several issues including covers on smoke detectors, caps on sprinklers, missing escutcheons in the showers/RR, missing ceiling tile at some locations, site work is incomplete, missing FE at the penthouse, non-functional emergency light at womens 7th floor, missing FE 2nd floor, need to add an emergency light at the intermediate floor west exit, the fire command center does not meet the req. min ft2, provide key and map in the knox box, need to test dedicated phone line in the command center, provide signage at the exit door to the alley, egress doors at the ground level stairway discharge may exceed allowable force to open per IFC 2003. Not all items reviewed at this time.
|
BLD03-01845
| FIRE-Final Inspection | 4/24/2006 | 4/24/2006 | | A | |
|
|
For final status
|