ELE07-00216
| ELE-Aging Inspection | 4/24/2007 | 4/24/2007 | 4/24/2007 4:02:02 PM | | DONE |
|
|
see final
|
ELE07-00216
| Final | 4/24/2007 | 4/24/2007 | 4/24/2007 4:00:33 PM | P | PASS |
|
|
looked at sign, ok to final
|
ELE07-00331
| Final | 4/24/2007 | 4/24/2007 | 4/24/2007 3:17:42 PM | P | PASS |
|
|
Neil ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
ELE07-00642
| Electrical Rough-In | 4/24/2007 | 4/24/2007 | 4/24/2007 2:37:54 PM | P | PASS |
|
|
mike - above the garage ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok over garage
|
ELE07-01431
| Electrical Rough-In | 4/24/2007 | 4/24/2007 | 4/24/2007 1:57:13 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 4/24/2007 at 10:09:14 AM. Contact: ###-####. u/g under slab ok, see notes permit 07-01429
|
ELE07-01429
| Electrical Rough-In | 4/24/2007 | 4/24/2007 | 4/24/2007 1:55:19 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/24/2007 at 10:08:08 AM. Contact: ###-####. ok to cover service conduit under slab- center under stairs has total of 4 90 degree bends so no offsets allowed from meter or panel, 1 common meter pak with breakers shall be used for both addresses
|
ELE07-01092
| Electrical Rough-In | 4/24/2007 | 4/24/2007 | 4/24/2007 12:59:27 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy walls and clg ok to cover
|
ELE07-01323
| Temporary Service | 4/24/2007 | 4/24/2007 | 4/24/2007 12:29:12 PM | P | FAIL |
|
|
If you have any questions please contact Karl. Phone #: ###-#### Internet Inspection Request from: Vicki Moore called, left corr notice, nec 110.12(A) all unused openings shall be closed, 408.4 circuit directory shall be provided and be clear, concise, and explanatory, BCC job id sticker shall be posted
|
ELE07-00226
| ELE-Aging Inspection | 4/24/2007 | 4/24/2007 | 4/24/2007 10:42:15 AM | | DONE |
|
|
see final
|
ELE07-00226
| Final | 4/24/2007 | 4/24/2007 | 4/24/2007 10:41:29 AM | A | PASS |
|
|
looked at sign, ok to final
|
ELE07-00187
| Final | 4/24/2007 | 4/24/2007 | 4/24/2007 10:14:49 AM | A | PASS |
|
|
looked at sign, ok to final
|
ELE06-00919
| Electrical Rough-In | 4/24/2007 | 4/24/2007 | 4/24/2007 10:09:03 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 4/24/2007 at 7:16:37 AM. Contact: ###-####. stairway clg ok to cover
|
ELE06-01143
| Electrical Rough-In | 4/24/2007 | 4/24/2007 | 4/24/2007 9:48:15 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 4/24/2007 at 7:19:05 AM. Contact: ###-####. front kitchen area, baths, 1 office - clgs ok to cover
|
ELE07-01438
| Electrical Rough-In | 4/23/2007 | 4/24/2007 | 4/24/2007 8:57:47 AM | A | PASS |
|
|
POOL BONDING Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack pool bonding ok
|
ELE06-03096
| Final | 4/23/2007 | 4/24/2007 | 4/24/2007 8:32:47 AM | A | PASS |
|
|
any questions please call Mike Dale Phone #: ###-#### x0000 Internet Inspection Request from: Sandee Johnson corr made, ok to final, no card signed
|
ELE06-03098
| Final | 4/23/2007 | 4/24/2007 | 4/24/2007 8:32:03 AM | A | PASS |
|
|
any questions please call Mike Dale Phone #: ###-#### x0000 Internet Inspection Request from: Sandee Johnson corr made, ok to final, no card signed
|
ELE06-03097
| Final | 4/23/2007 | 4/24/2007 | 4/24/2007 8:31:10 AM | A | PASS |
|
|
any questions please call Mike Dale Phone #: ###-#### x0000 Internet Inspection Request from: Sandee Johnson corr made, ok to final, no card signed
|