Inspections for the day of: Tuesday, April 24, 2007.
Number of inspections: 6
Percentage of inspections complete: 83 %
Percentage of inspections not complete: 17 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00595 INSP-Alarm Testing4/17/20074/18/2007 P 
don - after 5p, said he talked to forrest; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
FIR06-00594 FIR-Aging Inspection4/24/20074/24/20075/1/2007 12:30:28 PM DEFR
FIR06-00639 INSP-Final Inspection4/23/20074/24/20074/24/2007 9:06:52 PMAFAIL
Noted several items in need of correction prior to final including painted heads at various locations, missing flex couplings at the standipe risers in the stairwells, mixed head types in the south stairway, missing escutcheons at some locations, leaking head at the model unit bathroom, forward flow completed okay, missing automatic ball drip at the FDC check, need to test AFS monitoring as well.
FIR07-00254 INSP-Sprinkler Rough-in4/24/20074/24/20074/24/2007 2:22:03 PMPFAIL
Noted two areas are overspaced, one head is overspaced off an adjacent wall, missing one head as indicated on approved plans, all remaining areas are okay for cover.
FIR07-00284 INSP-Sprinkler Rough-in4/24/20074/24/20074/24/2007 2:18:29 PMPPART
Fire sprinkler work is approved for cover.
FIR07-00239 INSP-Sprinkler Rough-in4/23/20074/24/20074/24/2007 2:17:03 PMAPASS
Fire sprinkler system modifications are acceptable, rough-in is okay for cover at the drop and hard lid ceilings, final pending completion of ceilings and installation of escutcheons.