FIR08-00169
| INSP-Final Inspection | 4/23/2008 | 4/24/2008 | 4/25/2008 11:02:41 AM | A | FAIL |
|
|
Missing upright heads at the concealed combustible spaces above the hard lid ceilings at the restrooms and electrical room as indicated to be installed per plan modification.
|
BLD08-00440
| FIRE-Final Inspection | 4/24/2008 | 4/24/2008 | 4/24/2008 3:48:41 PM | P | PASS |
|
|
Corrections verified for completion, fire life safety finaled.
|
BLD07-02826
| FIRE-Final Inspection | 4/23/2008 | 4/24/2008 | 4/24/2008 3:47:37 PM | A | NR |
|
|
Need project related fire sprinkler permit work finaled prior to life safety final approval, exit signs and EM lights tested okay.
|
BLD07-02825
| FIRE-Final Inspection | 4/23/2008 | 4/24/2008 | 4/24/2008 3:39:57 PM | A | FAIL |
|
|
Need to repair exit discharge lights at the east and west sides, one EM light at the womens restroom is not functional, missing permit final for project related fire sprinkler work.
|
FIR08-00177
| INSP-Final Inspection | 4/23/2008 | 4/24/2008 | 4/24/2008 3:36:33 PM | A | PASS |
|
|
Fire alarm passed field inspection, permit finaled.
|
FIR08-00199
| INSP-Final Inspection | 4/23/2008 | 4/24/2008 | 4/24/2008 3:35:44 PM | A | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
FIR08-00244
| INSP-Final Inspection | 4/23/2008 | 4/24/2008 | 4/24/2008 1:59:28 PM | A | PASS |
|
|
Fire sprinkler work passed field inspection, rough-in and final inspections completed in conjunction, as-builts for minor field modifications accepted, permit finaled.
|
BLD08-00428
| FIRE-Final Inspection | 4/23/2008 | 4/24/2008 | 4/24/2008 1:57:44 PM | A | FAIL |
|
|
Provide approved door hardware at two locations, lower the fire extinguisher to no higher than 48" AFF, relocate one exit sign per plan, repair one exit sign and EM light at the future cad classroom, path of egrees must remain clear, need to install field ceiling tile at sprinkler pendents.
|