Inspections for the day of: Friday, April 24, 2009.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-02516 FIRE-Final Inspection4/23/20094/24/20094/24/2009 4:57:45 PMAPASS
Fire life safety final inspection completed satisfactory, project related fire alarm and sprinkler permits finaled.
FIR09-00031 INSP-Final Inspection4/23/20094/24/20094/24/2009 4:56:33 PMAPASS
Fire sprinkler permit work passed final inspection, preaction system supervision tested okay, permit finaled.
FIR09-00167 INSP-Final Inspection4/24/20094/24/20094/24/2009 4:55:28 PMAPASS
Fire alarm system modifications and interconnections to the clean agent panel and preaction system passed inspection, permit finaled.
FIR09-00127 INSP-Sprinkler Rough-in/Hydro4/23/20094/24/20094/24/2009 4:53:56 PMPFAIL
Hydrostatic test for the new preaction system failed due to pressure loss at the guage per site inspection completed by T. Frost.
FIR09-00259 INSP-Sprinkler Rough-in4/24/20094/24/20094/24/2009 4:52:17 PMPPART
Overhead piping at the breakroom approved for cover per T. Frost.
FIR09-00008 INSP-Final Inspection4/24/20094/24/20094/24/2009 3:47:40 PMPPASS
Fire sprinkler permit work approved for final per T. Frost.
FIR09-00008 INSP-Supply line flush4/23/20094/24/20094/24/2009 3:46:53 PMPPASS
UG fire supply line flush completed acceptable per T. Frost.
FIR07-00524 INSP-Final Inspection4/23/20094/24/20094/24/2009 3:45:42 PMPPASS
SECOND VISIT for failed first inspection items completed today including retest of post indicator valve, retest for non-functional notification devices, testing for mag lock FA interconnection at the main entry doors, checked relocated 3rd floor manual pull stations, adjusted dB levels at ADA and staff restrooms, map at panel, and elevator controls, supervising station signals checked okay. Fire alarm permit finaled.
BLD09-00568 FIRE-Final Inspection4/24/20094/24/20094/24/2009 3:22:09 PMPFAIL
Exit signs and EM lighting at three locations are not functional, fire extinguishers have been serviced but need to be mounted on the wall when painting is completed including the 1st and 2nd levels, electrical junction boxes at various locations are uncovered, floor plan provided does not match actual layout, a racking permit will be required for storage over 8' - racking moved into the warehouse may not be used prior to approval. See items circled or underlined on permit documents for issues discussed.
FIR08-00094 INSP-Alarm Testing4/23/20094/24/20094/24/2009 1:39:55 PMADEFR
Overbooked, rescheduled per phone conversation.
FIR09-00156 INSP-Final Inspection4/23/20094/24/20094/24/2009 1:39:07 PMADEFR
Overbooked, rescheduled as discussed.
FIR09-00014 FIR-Aging Inspection4/24/20094/24/20094/24/2009 1:35:46 PM DONE
Need site inspection request when work is finished.
FIR08-00234 INSP-Final Inspection4/23/20094/24/20094/24/2009 1:34:01 PMAPASS
Monitor module for alarm condition tie-in at the existing parking garage panel tested okay per condition of agreement letter, smoke alarm retested okay at unit 901, new plan sheets with field modifications verified for changes at the basement and 1st floors, portions of fire alarm work not completed per the scope of this permit yet shown on stamped drawings are to be done under FIR08-00754 (existing parking structure notification devices, FS and FP monitoring, FJ, and east and west elevator control functions), NFPA 72 completion report recieved. NOTE: Contractor to provide revised 18th floor plan for field device location changes, faxed copy of supervising station signals report, NFPA 72 record of inspection and testing per review note #4, and current map at the panel when FIR08-00754 work is finished.
BLD06-02303 FIRE-Final Inspection4/23/20094/24/20094/24/2009 1:20:24 PMAFAIL
Missing fire code review notes for on site inspection, noted item #10 per IFC sec. 509 at the fire command center has not been installed, need to coordinate EM lighting and exit signage testing via generator backup with the electrician, project related fire sprinkler permit is not yet approved for final.
BLD08-01791 FIRE-Final Inspection4/23/20094/24/20094/24/2009 1:14:25 PMAPASS
Correction notice items field verified for compliance, fire life safety passed, notified contractor.
FIR09-00241 INSP-Final Inspection4/23/20094/24/20094/24/2009 1:12:54 PMAPASS
Fire sprinkler work passed site inspection, permit final approved.
FIR09-00262 INSP-Final Inspection4/23/20094/24/20094/24/2009 1:11:12 PMAPASS
Scope of work passed final inspection, fire sprinkler permit finaled.