Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00491 FIRE-Final Inspection4/24/20124/24/20124/24/2012 3:04:27 PMPFAIL
The new door hardware does not unlock in a single motion as required. The door swing in the common restroom corridor has not been addressed. The address and tagging of the fire extinguisher has been provided.
BLD12-00136 FIRE-Final Inspection4/23/20124/24/20124/24/2012 3:03:00 PMAFAIL
Resubmit information on the flammable/combustible liquid storage/quantity. Mount/provide 2A,10BC fire extinguishers at front and back of the space including the mezzanine with current inspection tags. Repair the exit sign/emergency light out the west exit. Relocate the exit sign/emergency light to the door opening leading out the north exit. Provide bollards and striping per the approved plans.