Inspections for the day of: Wednesday, April 24, 2013.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02323 ELE-Aging Inspection4/24/20134/24/20134/24/2013 4:43:28 PM DONE
Still under construction
ELE13-00997 Final4/24/20134/24/20134/24/2013 3:16:33 PMPNR
robert Phone #: ###-#### Heat pump unit not set
ELE13-00997 Electrical Rough-In4/24/20134/24/20134/24/2013 3:16:01 PMPPASS
robert Phone #: ###-#### Heat pump rough in ok
ELE13-00593 Final4/24/20134/24/20134/24/2013 2:47:40 PMPPASS
Phone #: ###-#### >> Inspection requested via web by HZ ZAHIC
Final ok
ELE12-02982 Electrical Rough-In4/23/20134/24/20134/24/2013 2:23:16 PMPPASS
Tony Phone #: ###-#### Parking garage ceiling pour as noted on print. Rough in ok cover
ELE13-00993 Electrical Rough-In4/24/20134/24/20134/24/2013 1:45:34 PMPPASS
Please call me half an hour before inspection to insure access thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Back patio door switches and light. rough in ok cover
GCE13-00030 GCE-Final4/24/20134/24/20134/24/2013 1:07:31 PMPPASS
Clay ###-#### Final ok
ELE13-00968 Final4/24/20134/24/20134/24/2013 12:30:46 PMPCANC
Please provide an inspection of the temporary service. Call John with any questions ###-####. Thank you and have a wonderful day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez Needed temp service
ELE13-00968 Temporary Service4/24/20134/24/20134/24/2013 12:29:58 PMPPASS
Please provide an inspection of the temporary service. Call John with any questions ###-####. Thank you and have a wonderful day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez
t/s o/h n ok
ELE13-00995 Final4/24/20134/24/20134/24/2013 12:20:42 PMPPASS
This site is on the west side of the State St. entrance to Jackson''s Convenience Station.
Wired a new power pedestal & new cool-ped phone cabinet for Century Link. Thanks!!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
Final ok
ELE13-00995 Rough-In Permanent Service4/24/20134/24/20134/24/2013 12:19:30 PMPPASS
This site is on the west side of the State St. entrance to Jackson''s Convenience Station.
Wired a new power pedestal & new cool-ped phone cabinet for Century Link. Thanks!!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
rough in ok. p/s u/g n ok
ELE13-00298 Final4/24/20134/24/20134/24/2013 11:16:20 AMAFAIL
Eric is the super for the job his number is ###-#### he will be up there and can let you in just give him a call. thank you Phone #: ###-#### >> Inspection requested via web by Neal Rumsey
Utility bond ground bar shall be installed.
Furnace flex shall be secured.
Down patio outdoor receptical shall be GFCI protected.
AC max fuse 30a, 40a installed
ELE13-00977 Electrical Rough-In4/23/20134/24/20134/24/2013 10:30:38 AMAPASS
bonding inspection
pool cover--light--Gazebo post--gutter Phone #: ###-#### >> Inspection requested via web by Kevin Koomler
Bonding for pool, pool light, gazebo posts, gutter rough in ok cover
ELE13-00986 Electrical Rough-In4/23/20134/24/20134/24/2013 10:08:36 AMAPASS
Underground inspection - contact is Ryan Sorich Phone #: ###-#### >> Inspection requested via web by Scott Campbell
Underground to flow switches and down man hole
ELE13-00968 Final4/24/20134/24/20134/24/2013 9:37:07 AMACANC
Please inspect the temporary service for connection by Idaho Power. If you have any questions please contact John Rowles ###-####. Phone #: ###-#### >> Inspection requested via web by Kevin Perez
Neede temp service insp.
ELE13-00968 Temporary Service4/24/20134/24/20134/24/2013 9:36:16 AMPFAIL
Please inspect the temporary service for connection by Idaho Power. If you have any questions please contact John Rowles ###-####. Phone #: ###-#### >> Inspection requested via web by Kevin Perez
250.24(A)(1)-The grounding electrode conductor connection shall be made at any accessible point from the load end of the service drop to and including the terminal or bus to which the grounded service conductor is connected at service disconnecting means.
ELE13-00685 Electrical Rough-In4/23/20134/24/20134/24/2013 8:41:25 AMAPASS
TRENCH INSPECTIONS Phone #: ###-#### >> Inspection requested via web by mike brown Pool underground rough in ok cover