ELE09-02323
| ELE-Aging Inspection | 4/24/2013 | 4/24/2013 | 4/24/2013 4:43:28 PM | | DONE |
|
|
Still under construction
|
ELE13-00997
| Final | 4/24/2013 | 4/24/2013 | 4/24/2013 3:16:33 PM | P | NR |
|
|
robert Phone #: ###-#### Heat pump unit not set
|
ELE13-00997
| Electrical Rough-In | 4/24/2013 | 4/24/2013 | 4/24/2013 3:16:01 PM | P | PASS |
|
|
robert Phone #: ###-#### Heat pump rough in ok
|
ELE13-00593
| Final | 4/24/2013 | 4/24/2013 | 4/24/2013 2:47:40 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by HZ ZAHIC Final ok
|
ELE12-02982
| Electrical Rough-In | 4/23/2013 | 4/24/2013 | 4/24/2013 2:23:16 PM | P | PASS |
|
|
Tony Phone #: ###-#### Parking garage ceiling pour as noted on print. Rough in ok cover
|
ELE13-00993
| Electrical Rough-In | 4/24/2013 | 4/24/2013 | 4/24/2013 1:45:34 PM | P | PASS |
|
|
Please call me half an hour before inspection to insure access thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Back patio door switches and light. rough in ok cover
|
GCE13-00030
| GCE-Final | 4/24/2013 | 4/24/2013 | 4/24/2013 1:07:31 PM | P | PASS |
|
|
Clay ###-#### Final ok
|
ELE13-00968
| Final | 4/24/2013 | 4/24/2013 | 4/24/2013 12:30:46 PM | P | CANC |
|
|
Please provide an inspection of the temporary service. Call John with any questions ###-####. Thank you and have a wonderful day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez Needed temp service
|
ELE13-00968
| Temporary Service | 4/24/2013 | 4/24/2013 | 4/24/2013 12:29:58 PM | P | PASS |
|
|
Please provide an inspection of the temporary service. Call John with any questions ###-####. Thank you and have a wonderful day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez t/s o/h n ok
|
ELE13-00995
| Final | 4/24/2013 | 4/24/2013 | 4/24/2013 12:20:42 PM | P | PASS |
|
|
This site is on the west side of the State St. entrance to Jackson''s Convenience Station. Wired a new power pedestal & new cool-ped phone cabinet for Century Link. Thanks!!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Final ok
|
ELE13-00995
| Rough-In Permanent Service | 4/24/2013 | 4/24/2013 | 4/24/2013 12:19:30 PM | P | PASS |
|
|
This site is on the west side of the State St. entrance to Jackson''s Convenience Station. Wired a new power pedestal & new cool-ped phone cabinet for Century Link. Thanks!!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell rough in ok. p/s u/g n ok
|
ELE13-00298
| Final | 4/24/2013 | 4/24/2013 | 4/24/2013 11:16:20 AM | A | FAIL |
|
|
Eric is the super for the job his number is ###-#### he will be up there and can let you in just give him a call. thank you Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Utility bond ground bar shall be installed. Furnace flex shall be secured. Down patio outdoor receptical shall be GFCI protected. AC max fuse 30a, 40a installed
|
ELE13-00977
| Electrical Rough-In | 4/23/2013 | 4/24/2013 | 4/24/2013 10:30:38 AM | A | PASS |
|
|
bonding inspection pool cover--light--Gazebo post--gutter Phone #: ###-#### >> Inspection requested via web by Kevin Koomler Bonding for pool, pool light, gazebo posts, gutter rough in ok cover
|
ELE13-00986
| Electrical Rough-In | 4/23/2013 | 4/24/2013 | 4/24/2013 10:08:36 AM | A | PASS |
|
|
Underground inspection - contact is Ryan Sorich Phone #: ###-#### >> Inspection requested via web by Scott Campbell Underground to flow switches and down man hole
|
ELE13-00968
| Final | 4/24/2013 | 4/24/2013 | 4/24/2013 9:37:07 AM | A | CANC |
|
|
Please inspect the temporary service for connection by Idaho Power. If you have any questions please contact John Rowles ###-####. Phone #: ###-#### >> Inspection requested via web by Kevin Perez Neede temp service insp.
|
ELE13-00968
| Temporary Service | 4/24/2013 | 4/24/2013 | 4/24/2013 9:36:16 AM | P | FAIL |
|
|
Please inspect the temporary service for connection by Idaho Power. If you have any questions please contact John Rowles ###-####. Phone #: ###-#### >> Inspection requested via web by Kevin Perez 250.24(A)(1)-The grounding electrode conductor connection shall be made at any accessible point from the load end of the service drop to and including the terminal or bus to which the grounded service conductor is connected at service disconnecting means.
|
ELE13-00685
| Electrical Rough-In | 4/23/2013 | 4/24/2013 | 4/24/2013 8:41:25 AM | A | PASS |
|
|
TRENCH INSPECTIONS Phone #: ###-#### >> Inspection requested via web by mike brown Pool underground rough in ok cover
|