Inspections for the day of: Wednesday, April 24, 2013.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00382 FIRE-Final Inspection4/23/20134/24/20134/25/2013 6:59:37 AMAFAIL
Mike actually wanted a conference. Items discussed was the need for emergency lighting in the stairwell from ther mezzanine and an exit sign at the bottom exterior exit door, provide verification from plan review that door 112B can be deleted, provide code compliant exit path from the new "Accounting" area (can not exit through open construction), provide a FIR permit for the connection of fire sprinkler control valves to the existing fire alarm system (new anti-freeze system and new riser).
FIR12-00749 INSP-Final Inspection4/24/20134/24/20134/24/2013 3:37:19 PMPFAIL
Piping has not been back filled. Troy was on his way to turn on water.
BLD12-01035 FIRE-Conference4/23/20134/24/20134/24/2013 3:35:38 PMPDONE
BRENT and I went over life safety requirements which included fire extinguishers, exit signs and fire dept access. Per the plans the fence is to be removed but in actuallity only part of it has been removed. I deferred alternates for access to plan review.
BLD13-00920 FIRE-Final Inspection4/24/20134/24/20134/24/2013 3:32:50 PMPCANC
Per Mike we need to reschedule for next morning so door guy can get work completed.
FIR13-00032 INSP-Sprinkler Rough-in4/23/20134/24/20134/24/2013 11:45:03 AMAPASS
Can final when the canopies are installed.
BLD12-02195 FIRE-Final Inspection4/23/20134/24/20134/24/2013 10:34:40 AMAFAIL
the remote annunciators are still not the correct ones.
BLD13-00920 FIRE-Final Inspection4/23/20134/24/20134/24/2013 9:14:47 AMAFAIL
Provide fire extinguisher with current inspection tag, remove the thumbturn deadbolt at the main exit (keyed ok) and provide single action hardware at the separation door.