Inspections for the day of: Thursday, April 24, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01991 ELE-Aging Inspection4/24/20144/24/20145/2/2014 2:54:52 PM CANC
Too busy
ELE14-00919 Electrical Rough-In4/24/20144/24/20144/24/2014 1:49:11 PMPPASS
Please call Lloyd for access ###-####
Thank you, Greg Phone #: ###-#### >> Inspection requested via web by Greg Idsinga Wall rough in ok cover
ELE13-03142 Electrical Rough-In4/24/20144/24/20144/24/2014 12:43:43 PMPPASS
Drop lids Phone #: ###-#### >> Inspection requested via web by kendall bender Rough in ok cover
ELE14-01021 Electrical Rough-In4/24/20144/24/20144/24/2014 11:38:48 AMAPASS
trench insp.
I should be there by 8:15 or sooner to install pipe.
Go to gate on east side of yard go in and look left. Phone #: ###-#### >> Inspection requested via web by Mike Cole Rough in ok cover
ELE14-00993 Rough-In Permanent Service4/23/20144/24/20144/24/2014 10:14:00 AMAFAIL
If no one in home check room above garage for owners Phone #: ###-#### >> Inspection requested via web by Larry 300.4(A)(2)- NM cable shall be ran in a notch or hole bored through stud not on surface with nail plate tacked over top.
300.4- NM cable ran through holes bored holes that are less than 1 1/4" from framing surface shall be protected from physical damage.
210.52(B)(2)- The two or mor small appliance branch circuits specified in 210.52 (B)(1) shall have no other outlets.
406.3(D)- grounding tye receptical outlets installed on non grounded circuits shall have GFCI protection
ELE14-00879 Final4/23/20144/24/20144/24/2014 9:26:24 AMAPASS
Phone #: ###-#### >> Inspection requested via web by jamie berg Final ok
ELE14-01017 Rough-In Permanent Service4/23/20144/24/20144/24/2014 9:04:32 AMAPASS
Contact journeyman Jason Gaythwaite @###-#### prior to going to inspection. Thank you Phone #: ###-#### >> Inspection requested via web by Kelly Felin Service rough in ok.
p/s o/h n ok
ELE14-00859 Final4/24/20144/24/20144/24/2014 8:51:24 AMAFAIL
call Art with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack 210.8- receptical outlets located with in 6' of sink shall have GFCI protection.
110.3- 4 receptical outlets not working.