Inspections for the day of: Monday, April 24, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00037 Electrical Rough-In4/24/20174/24/20174/24/2017 2:53:06 PMPPASS
Ceiling Rough in Inspection for Building 7
Contact Dan Hutchinson @ ###-#### or ###-####
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
BLDG 7 all units rough in ok cover
ELE17-01025 Temporary Service4/23/20174/24/20174/24/2017 2:19:00 PMAPASS
Phone #: ###-#### Inspection requested via web by Tracy Robertson
t/s u/g n ok
ELE17-01176 Temporary Service4/24/20174/24/20174/24/2017 2:03:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE17-01061 Rough-In Permanent Service4/21/20174/24/20174/24/2017 1:55:34 PMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE17-01117 Rough-In Permanent Service4/21/20174/24/20174/24/2017 1:13:46 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE17-01124 Rough-In Permanent Service4/24/20174/24/20174/24/2017 10:12:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by kevin blackmon
IBC- Required smoke detectors 3 boxed but not wired on main floor.
200.6- Basement panel grounded conductor used for ungrounded shall be identified other than white.
300.4- Basement SER nail plate where 1 1/4" not maintained above panel.
ELE17-00127 Final4/20/20174/24/20174/24/2017 9:43:46 AMAFAIL
garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman
110.3- Devices shall be wired as per manufacturers instructions. 4 receptacles not working in theater, pantry light not working, all outdoor receptacles have reverse polarity.
210.52(C)- No point on kitchen counter shall be more than 24" from a receptacle. Counter by window 6' 4" between recepts.
210.52(D)- Master vanity receptacles serving basins shall be located on wall or cabinet adjacent to basin.
422.30- Range hood shall have an accessible disconnecting means. 110.25 lockout acceptable.