ELE19-00652
| Electrical Rough-In | 4/24/2019 | 4/24/2019 | 4/24/2019 2:39:22 PM | P | PASS |
|
|
Grid ceiling Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Bar grid rough in ok cover
|
ELE19-01075
| Final | 4/24/2019 | 4/24/2019 | 4/24/2019 2:08:41 PM | P | PASS |
|
|
Need grid inspection as well please. Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok
|
ELE19-01075
| Electrical Rough-In | 4/24/2019 | 4/24/2019 | 4/24/2019 2:08:14 PM | P | PASS |
|
|
Need grid inspection as well please. Phone #: ###-#### Inspection requested via web by Dean Gernaat Grid rough in ok cover
|
ELE18-02369
| Electrical Rough-In | 4/23/2019 | 4/24/2019 | 4/24/2019 1:51:31 PM | P | PASS |
|
|
Bank Canopy hardlid, two vestibule hardlid, 1st ceiling t-grid inspection. Call Joey C prior to arrival Phone #: ###-#### Inspection requested via web by Scott Campbell Vestibules and grid not ready, Bank canopy hard lid rough in ok cover
|
ELE19-01460
| Final | 4/23/2019 | 4/24/2019 | 4/24/2019 12:14:09 PM | A | PASS |
|
|
Electrical panel is on back of house under covered patio. AC disconnect is on front right side of house. A service outlet for equipment is located around gated fence behind AC. Please contact with questions. MC was used to run branch circuit. Conductors are THWN. Phone #: ###-#### Inspection requested via web by Ben Garner Final ok
|
ELE18-04683
| Final | 4/23/2019 | 4/24/2019 | 4/24/2019 11:38:25 AM | A | FAIL |
|
|
Lockbox code is 470916 Phone #: ###-#### Inspection requested via web by Troy Cobb BCC 4-05-32- Code violations not to be retained. Remove exposed wire tapped off upstairs and luminaire on south east corner. 110.3- Receptacle outlet not working down wall from kitchen counter. 314.21- repair drywall so that gap around boxes does not exceed 1/8"
|
ELE18-04231
| Final | 4/23/2019 | 4/24/2019 | 4/24/2019 10:54:42 AM | A | PART |
|
|
Please final units 101, 103, 105, 107, 201 ; 203. Any questions, please call Mike Brown ###-#### Phone #: ###-#### Inspection requested via web by Bonnie Page Ranges and dryer cords require installation to be done by electrical contractor. 250.140- Bonding strap shall be removed for 4 wire installation. Will check in future. 225.31 &32- A disconnecting means shall be provided for all ungrounded conductors that supply structure and shall be located on such structure. Units noted TCO ok
|
ELE19-01075
| Final | 4/23/2019 | 4/24/2019 | 4/24/2019 9:48:05 AM | A | FAIL |
|
|
Grid inspection and electrical final Lock box code 8463 located on the hand rail in stairwell Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.8- All receptacles located with in 6' of break room sink ( when set) shall have GFCI protection. 314.25- All boxes above grid shall have covers installed. Office 1, hallway.
|
ELE19-00934
| Electrical Rough-In | 4/23/2019 | 4/24/2019 | 4/24/2019 9:17:43 AM | A | PASS |
|
|
Ceiling rough-in Phone #: ###-#### Inspection requested via web by Steven Ragan Grid rough in ok cover
|