Inspections for the day of: Wednesday, April 24, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00652 Electrical Rough-In4/24/20194/24/20194/24/2019 2:39:22 PMPPASS
Grid ceiling Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Bar grid rough in ok cover
ELE19-01075 Final4/24/20194/24/20194/24/2019 2:08:41 PMPPASS
Need grid inspection as well please. Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok
ELE19-01075 Electrical Rough-In4/24/20194/24/20194/24/2019 2:08:14 PMPPASS
Need grid inspection as well please. Phone #: ###-#### Inspection requested via web by Dean Gernaat
Grid rough in ok cover
ELE18-02369 Electrical Rough-In4/23/20194/24/20194/24/2019 1:51:31 PMPPASS
Bank Canopy hardlid, two vestibule hardlid, 1st ceiling t-grid inspection. Call Joey C prior to arrival Phone #: ###-#### Inspection requested via web by Scott Campbell
Vestibules and grid not ready,
Bank canopy hard lid rough in ok cover
ELE19-01460 Final4/23/20194/24/20194/24/2019 12:14:09 PMAPASS
Electrical panel is on back of house under covered patio. AC disconnect is on front right side of house. A service outlet for equipment is located around gated fence behind AC. Please contact with questions. MC was used to run branch circuit. Conductors are THWN. Phone #: ###-#### Inspection requested via web by Ben Garner Final ok
ELE18-04683 Final4/23/20194/24/20194/24/2019 11:38:25 AMAFAIL
Lockbox code is 470916 Phone #: ###-#### Inspection requested via web by Troy Cobb
BCC 4-05-32- Code violations not to be retained. Remove exposed wire tapped off upstairs and luminaire on south east corner.
110.3- Receptacle outlet not working down wall from kitchen counter.
314.21- repair drywall so that gap around boxes does not exceed 1/8"
ELE18-04231 Final4/23/20194/24/20194/24/2019 10:54:42 AMAPART
Please final units 101, 103, 105, 107, 201 ; 203. Any questions, please call Mike Brown ###-#### Phone #: ###-#### Inspection requested via web by Bonnie Page
Ranges and dryer cords require installation to be done by electrical contractor.
250.140- Bonding strap shall be removed for 4 wire installation. Will check in future.
225.31 &32- A disconnecting means shall be provided for all ungrounded conductors that supply structure and shall be located on such structure.
Units noted TCO ok
ELE19-01075 Final4/23/20194/24/20194/24/2019 9:48:05 AMAFAIL
Grid inspection and electrical final
Lock box code 8463 located on the hand rail in stairwell Phone #: ###-#### Inspection requested via web by Dean Gernaat
210.8- All receptacles located with in 6' of break room sink ( when set) shall have GFCI protection. 314.25- All boxes above grid shall have covers installed. Office 1, hallway.
ELE19-00934 Electrical Rough-In4/23/20194/24/20194/24/2019 9:17:43 AMAPASS
Ceiling rough-in Phone #: ###-#### Inspection requested via web by Steven Ragan Grid rough in ok cover