Inspections for the day of: Monday, April 25, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01393 Permanent Service4/22/20054/25/20054/25/2005 12:00:00 AMAFAIL
jack ###-#### cor. posted met contractor 230.2 building shall have only one p/s 4/25/2005 10:39:52 AM
ELE05-00980 Final4/22/20054/25/20054/25/2005 12:00:00 AMAPASS
We have already had a Rough In that passed on 4-6-05. Would like to final the electrical on the remodel at this location. Thank you ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok card signed done by 412 4/25/2005 11:39:41 AM
ELE05-01395 Temporary Service4/22/20054/25/20054/25/2005 12:00:00 AMAFAIL
brian-- ###-#### cor. posted called 110.12(C) clean t/s, 110.3(B) use manufactures listed breakers only 4/25/2005 8:17:35 AM
ELE05-01360 Temporary Service4/22/20054/25/20054/25/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 4/22/2005 at 3:19:54 PM. Contact: ###-####. t/s u/g new ok 4/25/2005 10:29:59 AM
ELE05-01075 Rough-In Permanent Service4/22/20054/25/20054/25/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 4/22/2005 at 3:24:17 PM. Contact: ###-####. cor. posted called 210.52(B) remove outside recept from kit circuit, 314.3 metal raceway not allowed in plastic box, 210.52(D) bath recept shall not be more than 12" below basin top, clean off copper and call for concrete cover inspection for electrode 4/25/2005 10:33:20 AM
ELE05-01324 Permanent Service4/25/20054/25/20054/25/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 4/25/2005 at 6:43:35 AM. Contact: ###-####. cor. posted called 250.92 shall bond metal raceway bottom of meterbase note there might be more water piping to bond dont know what will be done with old or new piping 4/25/2005 8:57:44 AM
ELE05-01204 Electrical Rough-In4/25/20054/25/20054/25/2005 12:00:00 AMPFAIL
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore--call 1st before insp --after 12:30 not there ,,,, 2nd cor. posted
314.16 box fill , 210.52(B) remove DW from kit circuit, provide required circuit for DW, 334.30 staple romex where required,334.24 shall not bend romex less than 5 times diameter, uncover all wiring covered before inspection, shall wire smoke detectors as building code states shall be interlocked called J Storey, note told owner again he needs book on basic wiring and this is only a partial correction . correction notice posted for work done without permit or inspection this is prior work no violations to be retained p/s and sub panel added in garage also needs to update permit to match # of rooms work was done in 4/25/2005 3:36:04 PM
ELE05-01042 Final4/25/20054/25/20054/25/2005 12:00:00 AMPFAIL
lars; Phone #: ###-#### Internet Inspection Request from: Barbara Moore plans changed from time r/i needs outlet for wall spacing dinning rm was supposed to be a builtin bench, it is not called contractor will correct and call forreinspection 4/25/2005 2:16:09 PM
ELE05-01403 Temporary Service4/25/20054/25/20054/25/2005 12:00:00 AMPFAIL
jim-- ###-#### cor. posted inside of t/s called 240.24(A) t/s too high 6 ft 7" to highest breaker position, 110.3(B),550.33&11(D) shall provide 100 amp to job trailer as nameplate states, 550.32(A) service shall be within 30ft of trailer 4/25/2005 1:59:42 PM
ELE04-04122 Permanent Service4/25/20054/25/20054/25/2005 12:00:00 AMPCANC
Steve Sellers Contact with any questions or concerns; Phone #: ###-#### Internet Inspection Request from: Samantha Patterson ran out of time will do 04-26-05 AM 4/25/2005 5:01:33 PM
ELE05-01405 Conference4/25/20054/25/20054/25/2005 12:00:00 AMPDONE
michael work ###-#### or will be at home after 3:30 call this # ###-#### ok 4/25/2005 4:45:47 PM
ELE05-01395 Temporary Service4/25/20054/25/20054/25/2005 12:00:00 AMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s o/h new ok 4/25/2005 1:52:04 PM
ELE05-01409 Permanent Service4/25/20054/25/20054/25/2005 12:00:00 AMPPASS
kevin ###-#### p/s o/h rec. ok 4/25/2005 2:51:43 PM
ELE05-00989 Final4/25/20054/25/20054/25/2005 12:00:00 AMPPASS
final on swimming pool Internet Inspection Request from: Andy Rose ok 4/25/2005 12:50:45 PM