Inspections for the day of: Monday, April 25, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01379 Temporary Service4/22/20054/25/20054/25/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn t/s u/g n ok 4/25/2005 10:18:47 AM
ELE05-01390 Temporary Service4/22/20054/25/20054/25/2005 12:00:00 AMAFAIL
rowdy ###-#### called contr, left message , 250.24(B) main bonding jumper shall connect grounded conductor to gndg electrode conductor, re-inspection fee due 4/25/2005 8:06:51 AM
ELE05-01226 Rough-In Permanent Service4/22/20054/25/20054/25/2005 12:00:00 AMACANC
allen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see added insp for ric only 4/25/2005 9:43:17 AM
ELE05-01396 Electrical Rough-In4/22/20054/25/20054/25/2005 12:00:00 AMAPASS
###-#### dick called contr about 1 1/4" ric ok 4/25/2005 8:43:56 AM
ELE05-00150 Final4/22/20054/25/20054/25/2005 12:00:00 AMAPASS
ALAN; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final 4/25/2005 9:56:08 AM
ELE04-03889 Rough-In Permanent Service4/24/20054/25/20054/25/2005 12:00:00 AMACANC
Please provide inspection and sticker to existing meter stack for tenant space "c" so we may call Idaho power. to plug in a meter. Rough in inspection was accomplished but a sticker was not placed on meter section. Thank you...; Phone #: ###-#### Internet Inspection Request from: David Mackey ri already done, see added for p/s 4/25/2005 8:03:10 AM
ELE05-01370 Electrical Rough-In4/25/20054/25/20054/25/2005 12:00:00 AMAPASS
please inspect the whole space for rough-in...somehow we did not get the ceiling inspected and could not cover need done asap; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ceiling ok to cover 4/25/2005 9:07:09 AM
ELE04-03889 Permanent Service4/25/20054/25/20054/25/2005 12:00:00 AMAPASS
p/s off exst meter pak n ok
ELE05-01226 Electrical Rough-In4/25/20054/25/20054/25/2005 12:00:00 AMAPASS
ric for u/g conduit ok
ELE05-01390 Temporary Service4/25/20054/25/20054/25/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 4/25/2005 at 9:59:05 AM. Contact: ###-####. corrections made t/s u/g n ok 4/25/2005 12:13:11 PM
ELE05-00071 Final4/25/20054/25/20054/25/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 4/25/2005 at 10:04:35 AM. Contact: ###-####. called contr left survey, 352.30(A) rnc shall be supported within 3'-0 of conduit termination, 406.4(A) recpts shall be rigidly held 4/25/2005 12:48:24 PM
ELE05-01290 Final4/25/20054/25/20054/25/2005 12:00:00 AMPCANC
There is no roof access -- you will need a 12' extension ladder. Work was done from north face of building around to west face all on the roof. Units are numbered 5 (just a re-wire)and 8(disconnect)and a sub-panel. Any questions please call. Thank you!!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney called contr to meet at job with their ladder, they will call back in 4/25/2005 2:50:51 PM
ELE05-01392 Permanent Service4/25/20054/25/20054/25/2005 12:00:00 AMPCANC
final on service upgrade Internet Inspection Request from: Andy Rose nh, called contr, he said he will re-schedule 4/25/2005 4:30:59 PM
ELE05-01098 Electrical Rough-In4/25/20054/25/20054/25/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 4/25/2005 at 11:09:35 AM. Contact: ###-####. called contr, left corr notice, some items not done from 1st notice, some changes made, 314.3 box shall not use metal raceway unless listed, 314.20 box shall be flush with combustible material, 314.17(C) nm cable shall be stapled within 8" of box 4/25/2005 2:04:21 PM
ELE05-00739 Electrical Rough-In4/25/20054/25/20054/25/2005 12:00:00 AMPPASS
CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok to cover ceiling 4/25/2005 3:55:23 PM
ELE05-01305 Final4/18/20054/25/20054/19/2005 7:33:25 AMACANC
Late morning.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer Inspection cancelled from web by: Dana Moyer