ELE05-01379
| Temporary Service | 4/22/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Bob Glenn t/s u/g n ok 4/25/2005 10:18:47 AM
|
ELE05-01390
| Temporary Service | 4/22/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | FAIL |
|
|
rowdy ###-#### called contr, left message , 250.24(B) main bonding jumper shall connect grounded conductor to gndg electrode conductor, re-inspection fee due 4/25/2005 8:06:51 AM
|
ELE05-01226
| Rough-In Permanent Service | 4/22/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | CANC |
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see added insp for ric only 4/25/2005 9:43:17 AM
|
ELE05-01396
| Electrical Rough-In | 4/22/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | PASS |
|
|
###-#### dick called contr about 1 1/4" ric ok 4/25/2005 8:43:56 AM
|
ELE05-00150
| Final | 4/22/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | PASS |
|
|
ALAN; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final 4/25/2005 9:56:08 AM
|
ELE04-03889
| Rough-In Permanent Service | 4/24/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | CANC |
|
|
Please provide inspection and sticker to existing meter stack for tenant space "c" so we may call Idaho power. to plug in a meter. Rough in inspection was accomplished but a sticker was not placed on meter section. Thank you...; Phone #: ###-#### Internet Inspection Request from: David Mackey ri already done, see added for p/s 4/25/2005 8:03:10 AM
|
ELE05-01370
| Electrical Rough-In | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | PASS |
|
|
please inspect the whole space for rough-in...somehow we did not get the ceiling inspected and could not cover need done asap; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ceiling ok to cover 4/25/2005 9:07:09 AM
|
ELE04-03889
| Permanent Service | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | PASS |
|
|
p/s off exst meter pak n ok
|
ELE05-01226
| Electrical Rough-In | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | A | PASS |
|
|
ric for u/g conduit ok
|
ELE05-01390
| Temporary Service | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/25/2005 at 9:59:05 AM. Contact: ###-####. corrections made t/s u/g n ok 4/25/2005 12:13:11 PM
|
ELE05-00071
| Final | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/25/2005 at 10:04:35 AM. Contact: ###-####. called contr left survey, 352.30(A) rnc shall be supported within 3'-0 of conduit termination, 406.4(A) recpts shall be rigidly held 4/25/2005 12:48:24 PM
|
ELE05-01290
| Final | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | P | CANC |
|
|
There is no roof access -- you will need a 12' extension ladder. Work was done from north face of building around to west face all on the roof. Units are numbered 5 (just a re-wire)and 8(disconnect)and a sub-panel. Any questions please call. Thank you!!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney called contr to meet at job with their ladder, they will call back in 4/25/2005 2:50:51 PM
|
ELE05-01392
| Permanent Service | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | P | CANC |
|
|
final on service upgrade Internet Inspection Request from: Andy Rose nh, called contr, he said he will re-schedule 4/25/2005 4:30:59 PM
|
ELE05-01098
| Electrical Rough-In | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/25/2005 at 11:09:35 AM. Contact: ###-####. called contr, left corr notice, some items not done from 1st notice, some changes made, 314.3 box shall not use metal raceway unless listed, 314.20 box shall be flush with combustible material, 314.17(C) nm cable shall be stapled within 8" of box 4/25/2005 2:04:21 PM
|
ELE05-00739
| Electrical Rough-In | 4/25/2005 | 4/25/2005 | 4/25/2005 12:00:00 AM | P | PASS |
|
|
CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok to cover ceiling 4/25/2005 3:55:23 PM
|
ELE05-01305
| Final | 4/18/2005 | 4/25/2005 | 4/19/2005 7:33:25 AM | A | CANC |
|
|
Late morning.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer Inspection cancelled from web by: Dana Moyer
|