ELE06-01203
| Electrical Rough-In | 4/24/2006 | 4/25/2006 | 4/25/2006 4:20:20 PM | P | PASS |
|
|
NEED 1ST FLOOR WALL INSPECTION ON NEW CONSTRUCTION. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH looked at first floor walls, told elect to strap at missing point by boxes, looked at 300hp compressor, said they need to see if listed assembly, service grounding ok, walls only 1st floor ok to cover
|
ELE06-01398
| Temporary Service | 4/25/2006 | 4/25/2006 | 4/25/2006 3:45:09 PM | P | PASS |
|
|
###-#### -rick corr made, t/s u/g n ok
|
ELE06-01029
| Rough-In Permanent Service | 4/25/2006 | 4/25/2006 | 4/25/2006 3:02:02 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier ric ok, p/s u/g n ok
|
ELE06-00482
| ELE-Aging Inspection | 4/25/2006 | 4/25/2006 | 4/25/2006 2:28:42 PM | | DONE |
|
|
checked job, suc
|
ELE06-00458
| Final | 4/25/2006 | 4/25/2006 | 4/25/2006 1:33:04 PM | P | PASS |
|
|
mike Note:if cant get in call; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE06-00369
| Final | 4/24/2006 | 4/25/2006 | 4/25/2006 12:01:37 PM | A | PASS |
|
|
Internet Inspection Request from: Tyler Bowen ok to final
|
ELE06-00244
| Final | 4/24/2006 | 4/25/2006 | 4/25/2006 11:40:59 AM | A | PASS |
|
|
Internet Inspection Request from: Tyler Bowen ok to final
|
ELE06-01409
| Electrical Rough-In | 4/24/2006 | 4/25/2006 | 4/25/2006 10:06:12 AM | A | PASS |
|
|
###-#### - mitch told contr about 1 1/4" and stapling, he will fix, ric ok, told owner to provide access to panel
|
ELE06-00938
| Final | 4/24/2006 | 4/25/2006 | 4/25/2006 9:36:47 AM | A | PASS |
|
|
SWIMMING POOL NOW READY FOR RE-INSPECTION. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall corr made, ok to final
|
ELE06-01417
| Temporary Service | 4/24/2006 | 4/25/2006 | 4/25/2006 8:54:43 AM | A | FAIL |
|
|
###-#### - shelly called contr, left corr notice, nec 110.34(A) min work space shall be 3' in front of elect equip, Note, locate grounding electrode, fee due
|
ELE06-01416
| Temporary Service | 4/24/2006 | 4/25/2006 | 4/25/2006 8:53:40 AM | A | FAIL |
|
|
###-#### - shelley called contr, left corr notice, nec 250.50 shall install grounding electrode, fee due
|
ELE06-01407
| Rough-In Permanent Service | 4/24/2006 | 4/25/2006 | 4/25/2006 8:26:50 AM | A | FAIL |
|
|
###-#### wired for townhouse, not duplex called contr, they said to ask for inspection and see what happens.
|
ELE06-01367
| Rough-In Permanent Service | 4/21/2006 | 4/25/2006 | 4/24/2006 8:01:48 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 4/21/2006 at 3:41:19 PM. Disp set to [CANC] by a contractor via Hello! on Apr 24 2006 8:01AM.
|