Inspections for the day of: Wednesday, April 25, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Johnson
TitlePLM-INSPECTOR
Phone #794-9476
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS07-00090 PLM-Conference4/25/20074/25/20074/26/2007 11:00:35 AMPDONE
dena ###-#### was call out 815 s. curtis to investigate strong sewer smell between trailer space 43 and 44 investigation led to trailer space 44 got permission from trailer owner to remove trailer skirting to look finding that trailer drain line some how had been disconnected from trailer park sewer drain line. I moved drain line back in to park sewer line so it would drain Dena notified central district health
PLM05-04309 Plumbing Rough-in4/25/20074/25/20074/26/2007 8:40:26 AMPPART
Scheduled by a contractor via Hello! on 4/25/2007 at 9:59:43 AM. Contact: ###-####. 8th floor dwv and over head venting for room,s 87107,08,09,17,18,19,20,22,and 24 test ok . 2nd floor south tower remodel dwv and over head venting for room,s 22100,22101,22017,20,23,and 26, 0k
PLM07-01338 Sprinkler (Final)4/25/20074/25/20074/25/2007 3:07:12 PMPPASS
chad - after 3:00 please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
PLM07-01337 Sprinkler (Final)4/25/20074/25/20074/25/2007 3:06:07 PMPPASS
chad - after 3:00 please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
PLM07-01195 Plumbing Rough-in4/24/20074/25/20074/25/2007 2:39:42 PMPFAIL
RUSS; Phone #: ###-#### Internet Inspection Request from: Victoria Beall need to move all water lines from outside wall,s and replumb need to remove drain piping from low heel 90 to water closet and tie in below vent to water closet need to repipe vent to shower
PLM07-01208 Plumbing Rough-in4/25/20074/25/20074/25/2007 1:34:27 PMPPASS
All American Plumbing ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
PLM07-01311 Sprinkler (Final)4/24/20074/25/20074/25/2007 1:22:43 PMPFAIL
eric ###-#### need to use approved material from control valves to back flow device need to change 100 psi piping to at least 160 psi
PLM07-01312 Groundwork4/25/20074/25/20074/25/2007 11:13:06 AMPPASS
Jim Henderson is the field contact Phone #: ###-#### Internet Inspection Request from: Heidi Mallet new water to job trailer test ok need to have water company tutn water on so double check for job trailer premius protection can be tested and certified
PLM07-01281 Plumbing Rough-in4/24/20074/25/20074/25/2007 9:37:43 AMAFAIL
JOB # 10624 Phone #: ###-#### Internet Inspection Request from: Ann Marie Reyes need to move pex water piping from can light,s in kit. area contractor to recall when ready
PLM07-01280 Plumbing Rough-in4/24/20074/25/20074/25/2007 9:09:15 AMAPASS
JOB # 10623 Phone #: ###-#### Internet Inspection Request from: Ann Marie Reyes