Inspections for the day of: Wednesday, April 25, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01469 Electrical Rough-In4/25/20074/25/20074/25/2007 4:02:20 PMPPASS
Rough in Inspection for office area Phone #: ###-#### Internet Inspection Request from: Alan Lusk walls except baths ok to cover
ELE07-01473 Rough-In Permanent Service4/25/20074/25/20074/25/2007 2:51:47 PMPFAIL
Chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, nec 250.86 metal boxes shall be grounded, 300.4(A)&(D) edge of bored holes, mc cable, and ent shall be 1 1/4" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of box, 250.52(A)(3) shall utilize concrete encased electrode, 110.22 disconnects shall be identified and dufficient durability for conditions-inside and outside, BCC address shall be posted, job id sticker shall be posted, each meter requires permit, may need house panel
ELE07-01017 Final4/25/20074/25/20074/25/2007 1:59:04 PMPPASS
Justin; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections made, ok to final, signed card
ELE06-02818 Final4/25/20074/25/20074/25/2007 1:18:24 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr made, ok to final
ELE07-00525 Electrical Rough-In4/25/20074/25/20074/25/2007 12:26:43 PMPPASS
H Z garage; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover u/g to garage and ric ok
ELE07-01428 Electrical Rough-In4/24/20074/25/20074/25/2007 11:00:12 AMAPASS
CHARLIE - LATE MORNING; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to pour slab, said ok to call when done
ELE07-00750 Final4/24/20074/25/20074/25/2007 10:43:52 AMAPASS
contact info gene ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final
ELE07-00751 Final4/24/20074/25/20074/25/2007 10:40:19 AMAPASS
contact info ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final
ELE07-01401 Temporary Service4/24/20074/25/20074/25/2007 9:50:08 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson called left message, nec 110.12(C) there shall be no broken parts, 50a recpt, panel door
ELE06-04140 Final4/24/20074/25/20074/25/2007 9:28:16 AMANR
kelly ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called to change to p/s, then can final with power on
ELE06-04140 Permanent Service4/25/20074/25/20074/25/2007 9:27:08 AMAPASS
kelly ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr to provide access for gec connection, and to change gec abrasion protection, p/s u/g n ok
ELE07-01456 Final4/24/20074/25/20074/25/2007 8:54:08 AMAPASS
electrician - Ron Chaney Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok to final
ELE07-01017 Final4/24/20074/25/20074/25/2007 8:38:55 AMAPART
justin; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover clgs, left corr notice, nec 110.12(A) close openings, 408.4 circuit directory shall be done, 110.3 shall fix recpts and supply power to office
ELE07-01465 Electrical Rough-In4/24/20074/25/20074/25/2007 7:56:29 AMAFAIL
Rough Inspect underground for pool lights and sub panel inspection. Please Call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson called contr about u/g from pad, nec 352.26 there shall not be over 360 degree bends in rnc, 680.10 there shall be no u/g wiring within 5' of inside wall of pool, told pool man could work around pool shell only
ELE06-03959 Conference4/23/20074/25/20074/24/2007 8:16:11 AMADONE
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked about transformer secondary overcurrent protection and disconnect location