FIR06-00595
| INSP-Alarm Testing | 4/17/2007 | 4/18/2007 | | P | |
|
|
don - after 5p, said he talked to forrest; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
FIR06-00689
| FIR-Aging Inspection | 4/25/2007 | 4/25/2007 | 5/1/2007 12:31:28 PM | | DEFR |
|
|
|
FIR06-00595
| INSP-Alarm Testing | 4/23/2007 | 4/25/2007 | 4/26/2007 2:28:22 PM | P | DEFR |
|
|
See comments per field inspection by M. Timmerman.
|
BLD06-00323
| FIRE-Final Inspection | 4/25/2007 | 4/25/2007 | 4/26/2007 1:19:58 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD07-00469
| FIRE-Final Inspection | 4/25/2007 | 4/25/2007 | 4/25/2007 4:28:43 PM | P | PASS |
|
|
Life safety inspection passed.
|
FIR06-00657
| INSP-Alarm Testing | 4/24/2007 | 4/25/2007 | 4/25/2007 4:16:05 PM | P | PART |
|
|
Fire alarm testing completed satisfactory for the remodel areas except the unfinished autology room as circled on plans.
|
BLD07-00156
| FIRE-Final Inspection | 4/25/2007 | 4/25/2007 | 4/25/2007 2:22:57 PM | P | FAIL |
|
|
Need to install one missing exit sign and emergency light at one location as indicated on approved plans, provide approved hardware at the back storeroom door below the required exit sign.
|
FIR06-00302
| INSP-Final Inspection | 4/17/2007 | 4/25/2007 | 4/25/2007 1:28:04 PM | A | FAIL |
|
|
The wall post indicator supervisory switch is out of adjustment, tamper switches for riser control valves need to be non-latching.
|
MIS07-00087
| FIR-Final | 4/24/2007 | 4/25/2007 | 4/25/2007 12:35:30 PM | A | FAIL |
|
|
The fire extinguisher is overdue annual certification, three upright sprinklers at the front entryway are out of correct axis and need to be realigned for proper functionality.
|
FIR06-00495
| INSP-Final Inspection | 4/24/2007 | 4/25/2007 | 4/25/2007 12:03:08 PM | A | PART |
|
|
AFS monitoring, FACP, nac panels, first floor notification, detection and initiation tested today. Noted items in need of correction including correct size batteries at the main panel, dB level in the trash chute rooms, the mini horns in the residential units do not produce the required temporal pattern per review notes or NFPA 72, no elevator devices tested at this time, list of signals recieved to be verified at next scheduled inspection.
|