Inspections for the day of: Wednesday, April 25, 2007.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00595 INSP-Alarm Testing4/17/20074/18/2007 P 
don - after 5p, said he talked to forrest; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
FIR06-00689 FIR-Aging Inspection4/25/20074/25/20075/1/2007 12:31:28 PM DEFR
FIR06-00595 INSP-Alarm Testing4/23/20074/25/20074/26/2007 2:28:22 PMPDEFR
See comments per field inspection by M. Timmerman.
BLD06-00323 FIRE-Final Inspection4/25/20074/25/20074/26/2007 1:19:58 PMPPASS
Fire life safety finaled.
BLD07-00469 FIRE-Final Inspection4/25/20074/25/20074/25/2007 4:28:43 PMPPASS
Life safety inspection passed.
FIR06-00657 INSP-Alarm Testing4/24/20074/25/20074/25/2007 4:16:05 PMPPART
Fire alarm testing completed satisfactory for the remodel areas except the unfinished autology room as circled on plans.
BLD07-00156 FIRE-Final Inspection4/25/20074/25/20074/25/2007 2:22:57 PMPFAIL
Need to install one missing exit sign and emergency light at one location as indicated on approved plans, provide approved hardware at the back storeroom door below the required exit sign.
FIR06-00302 INSP-Final Inspection4/17/20074/25/20074/25/2007 1:28:04 PMAFAIL
The wall post indicator supervisory switch is out of adjustment, tamper switches for riser control valves need to be non-latching.
MIS07-00087 FIR-Final4/24/20074/25/20074/25/2007 12:35:30 PMAFAIL
The fire extinguisher is overdue annual certification, three upright sprinklers at the front entryway are out of correct axis and need to be realigned for proper functionality.
FIR06-00495 INSP-Final Inspection4/24/20074/25/20074/25/2007 12:03:08 PMAPART
AFS monitoring, FACP, nac panels, first floor notification, detection and initiation tested today. Noted items in need of correction including correct size batteries at the main panel, dB level in the trash chute rooms, the mini horns in the residential units do not produce the required temporal pattern per review notes or NFPA 72, no elevator devices tested at this time, list of signals recieved to be verified at next scheduled inspection.