Inspections for the day of: Wednesday, April 25, 2007.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00419 FIRE-Final Inspection4/24/20074/25/20075/1/2007 11:20:18 AMPFAIL
provide approved hardware and tag fire extinguishers
FIR07-00369 INSP-Final Inspection4/25/20074/25/20074/25/2007 6:30:06 PMPCANC
Per Don the electrical portion of the project was not correct yet. No inspection performed.
FIR05-00822 INSP-Sprinkler Rough-in4/25/20074/25/20074/25/2007 6:28:44 PMPPASS
See the city approved plans for locations of inspection and for corrections required.
BLD06-03151 FIRE-Final Inspection4/24/20074/25/20074/25/2007 1:52:06 PMAFAIL
Mount the fire extinguisher as discussed.
FIR07-00364 INSP-Sprinkler Rough-in4/24/20074/25/20074/25/2007 1:06:10 PMAPASS
The underground stub out is ok to cover. The trench has slough off onto the piping but from what I dug out it does appear to be 6"
FIR07-00231 INSP-Sprinkler Rough-in4/24/20074/25/20074/25/2007 10:41:48 AMAFAIL
Pendant heads are overspaced, hanger rod bent, retaining straps missing/not installed correctly missing heads. Notice posted to not cover sprinkler piping.