FIR07-00902
| INSP-Sprinkler Rough-in | 4/23/2008 | 4/25/2008 | 4/25/2008 4:46:02 PM | P | PART |
|
|
OH rough-in inspection completed for the second floor only at this time, see plans for areas not completed to date.
|
FIR08-00228
| INSP-Sprinkler Rough-in | 4/25/2008 | 4/25/2008 | 4/25/2008 4:36:40 PM | P | FAIL |
|
|
Noted two overspaced heads on a branch line at the east open office area, three heads at one conference room do not meet spacing requirements off adjacent walls, see as-built plans for red-lined annotations. The remainder of overhead install per the permit scope is approved for cover.
|
BLD08-00574
| FIRE-Final Inspection | 4/25/2008 | 4/25/2008 | 4/25/2008 4:29:12 PM | P | FAIL |
|
|
Remove the manual thumbturn at the main entry/exit door, provide door to remain unlocked signage, hardware at the restroom door is not approved.
|
BLD07-02826
| FIRE-Final Inspection | 4/25/2008 | 4/25/2008 | 4/25/2008 4:26:45 PM | P | PASS |
|
|
C/N items completed, fire life safety finaled.
|
BLD07-02825
| FIRE-Final Inspection | 4/25/2008 | 4/25/2008 | 4/25/2008 4:25:55 PM | P | PASS |
|
|
Corrections are finished, fire life safety passed final inspection.
|
FIR07-00894
| INSP-Sprinkler Rough-in | 4/23/2008 | 4/25/2008 | 4/25/2008 2:07:27 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory.
|
FIR08-00298
| INSP-Final Inspection | 4/25/2008 | 4/25/2008 | 4/25/2008 2:06:40 PM | P | PASS |
|
|
Fire sprinkler permit finaled-see FIR08-00071 for inspection notes and review comments/approved plans.
|
BLD07-02764
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 12:21:23 PM | A | PASS |
|
|
Noted corrections have been completed with the exception of the EM light at the basement exit stairs and hardware at the basement and 2nd floor restrooms- these items to be verified as agreed at the structural final.
|
FIR08-00241
| INSP-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 12:18:51 PM | A | FAIL |
|
|
The smoke detector at the kitchen side of the doors is not in compliance with NFPA 72 5.7.4.1 regarding proximity to the HVAC register.
|
FIR08-00071
| INSP-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 10:25:25 AM | A | PASS |
|
|
Noted corrections are complete, fire sprinkler work passed inspection, permit finaled.
|
FIR07-00521
| INSP-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 9:47:08 AM | A | PASS |
|
|
Fire sprinkler permit approved for final per inspection notes completed 7/27/07, doc. finaled.
|
FIR08-00044
| INSP-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 9:33:32 AM | A | PART |
|
|
Scope of fire alarm work tested okay including new a/v devices and manual pull stations, final pending relay for interconnection of the mag locks at the new lobby doors to the fire alarm system.
|
BLD07-03052
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 9:30:39 AM | A | FAIL |
|
|
The new lobby exit doors equipped with magnetic locks must comply with IBC 1008.1.3.4 items 1-6-specifically item #4 which has not been provided for, also need to repair the ceiling at the com. room adjacent to the east restroom for proper heat collection of the pendent sprinkler head and separation of sprinklered/non-sprinklered areas.
|
BLD08-00428
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 9:15:04 AM | A | PASS |
|
|
Items on correction notice verified for compliance, fire life safety passed.
|
BLD08-00573
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 9:13:43 AM | A | FAIL |
|
|
Remove the manual thumbturn at the main entry/exit door and provide signage above the door "door to remain unlocked while building is occupied", repair the non-functional EM light at the hallway, post suite address, provide approved hardware at the restroom door.
|