Inspections for the day of: Friday, April 25, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00902 INSP-Sprinkler Rough-in4/23/20084/25/20084/25/2008 4:46:02 PMPPART
OH rough-in inspection completed for the second floor only at this time, see plans for areas not completed to date.
FIR08-00228 INSP-Sprinkler Rough-in4/25/20084/25/20084/25/2008 4:36:40 PMPFAIL
Noted two overspaced heads on a branch line at the east open office area, three heads at one conference room do not meet spacing requirements off adjacent walls, see as-built plans for red-lined annotations. The remainder of overhead install per the permit scope is approved for cover.
BLD08-00574 FIRE-Final Inspection4/25/20084/25/20084/25/2008 4:29:12 PMPFAIL
Remove the manual thumbturn at the main entry/exit door, provide door to remain unlocked signage, hardware at the restroom door is not approved.
BLD07-02826 FIRE-Final Inspection4/25/20084/25/20084/25/2008 4:26:45 PMPPASS
C/N items completed, fire life safety finaled.
BLD07-02825 FIRE-Final Inspection4/25/20084/25/20084/25/2008 4:25:55 PMPPASS
Corrections are finished, fire life safety passed final inspection.
FIR07-00894 INSP-Sprinkler Rough-in4/23/20084/25/20084/25/2008 2:07:27 PMPPART
UG fire supply line flush completed satisfactory.
FIR08-00298 INSP-Final Inspection4/25/20084/25/20084/25/2008 2:06:40 PMPPASS
Fire sprinkler permit finaled-see FIR08-00071 for inspection notes and review comments/approved plans.
BLD07-02764 FIRE-Final Inspection4/24/20084/25/20084/25/2008 12:21:23 PMAPASS
Noted corrections have been completed with the exception of the EM light at the basement exit stairs and hardware at the basement and 2nd floor restrooms- these items to be verified as agreed at the structural final.
FIR08-00241 INSP-Final Inspection4/24/20084/25/20084/25/2008 12:18:51 PMAFAIL
The smoke detector at the kitchen side of the doors is not in compliance with NFPA 72 5.7.4.1 regarding proximity to the HVAC register.
FIR08-00071 INSP-Final Inspection4/24/20084/25/20084/25/2008 10:25:25 AMAPASS
Noted corrections are complete, fire sprinkler work passed inspection, permit finaled.
FIR07-00521 INSP-Final Inspection4/24/20084/25/20084/25/2008 9:47:08 AMAPASS
Fire sprinkler permit approved for final per inspection notes completed 7/27/07, doc. finaled.
FIR08-00044 INSP-Final Inspection4/24/20084/25/20084/25/2008 9:33:32 AMAPART
Scope of fire alarm work tested okay including new a/v devices and manual pull stations, final pending relay for interconnection of the mag locks at the new lobby doors to the fire alarm system.
BLD07-03052 FIRE-Final Inspection4/24/20084/25/20084/25/2008 9:30:39 AMAFAIL
The new lobby exit doors equipped with magnetic locks must comply with IBC 1008.1.3.4 items 1-6-specifically item #4 which has not been provided for, also need to repair the ceiling at the com. room adjacent to the east restroom for proper heat collection of the pendent sprinkler head and separation of sprinklered/non-sprinklered areas.
BLD08-00428 FIRE-Final Inspection4/24/20084/25/20084/25/2008 9:15:04 AMAPASS
Items on correction notice verified for compliance, fire life safety passed.
BLD08-00573 FIRE-Final Inspection4/24/20084/25/20084/25/2008 9:13:43 AMAFAIL
Remove the manual thumbturn at the main entry/exit door and provide signage above the door "door to remain unlocked while building is occupied", repair the non-functional EM light at the hallway, post suite address, provide approved hardware at the restroom door.