FIR07-01003
| FIR-Aging Inspection | 4/25/2008 | 4/25/2008 | 4/28/2008 2:00:55 PM | | NR |
|
|
Job not ready as per Mike Oswald. KR
|
BLD05-02539
| FIRE-Conference | 4/25/2008 | 4/25/2008 | 4/25/2008 4:44:06 PM | P | PASS |
|
|
Life safety passed.
|
FIR08-00049
| INSP-Final Inspection | 4/25/2008 | 4/25/2008 | 4/25/2008 3:40:40 PM | P | FAIL |
|
|
The removal of the fire sprinkler piping penatrating the hoods has been removed but not all of the holes have been sealed. The holes must be sealed.
|
FIR08-00129
| INSP-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 3:38:53 PM | A | FAIL |
|
|
The existing facp that was to be removed has not been removed. According to Bruce it appears now to be used as a security panel. It was set off prior to my arrival and per Bruce it annunciated a gate valve tamper. This panel can remain and be used as security but can not operate as a fire alarm panel as it apparently still is. Bruce was going to investigate. Eight additional duct smoke detectors have been added and as-builts had been provided. During testing of the first duct smoke detector the hvac unit did not shut down immediately as required per IMC chapter 6. Per the new technician all of the duct detectors did not shut down. Bruce and the electrician from Romar Electric were going to rewire the transformers so that they shutdown correctly. Bottom line was no items were tested beyond the first duct smoke detector.
|
BLD07-03081
| FIRE-Final Inspection | 4/25/2008 | 4/25/2008 | 4/25/2008 12:58:00 PM | P | PASS |
|
|
Life safety passed.
|
FIR07-01040
| INSP-Final Inspection | 4/25/2008 | 4/25/2008 | 4/25/2008 12:57:31 PM | P | PASS |
|
|
Permit finaled
|
BLD07-03081
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 12:45:32 PM | A | FAIL |
|
|
Provide the correct building address.
|
BLD08-00549
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 11:06:06 AM | A | FAIL |
|
|
ScheInspection was for units 305 and 357. Repair exit signs/emergency lights in both tenants. Provide annual inspection for the fire extinguishers in both tenants. Provide additional fire extinguisher near front (south end) of tenant 357. Sprinkler pendants are overspaced off of the south wall in the two existing offices of tenant 357(see approved plans). Repair the damaged electrical outlests. Provide sprinkler coverage beneath the south overhead door of tenant 357 because the door exceeds 4'-0". Remove the thumbturn locks from the restroom doors in tenant 305. Provide a racking permit for the 11'-6" racks located in tenant 305. Currently balloons, refrigerators, computers and toys (plastic) are being stored on wooden pallets within (floor level) the racks themselves. Storage is at 7'-0". Atleast two building columns have been positionded within the storage racks which requires sprinkler protection per NFPA 13. The duct smoke detectors in unit 305 are in a trouble condition and will need repaired. The fire alarm panel is in a trouble condition and will need repaired. Provide approved hardware on the south secondary exit door from tenant 305. Provide corrected upright fire sprinkler protection along both sides of the two new full height walls. Both sides of walls to be included.duled by a contractor via Hello! on 4/24/2008 at 4:32:29 PM. Contact: ###-####.
|
BLD08-00547
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 11:05:41 AM | A | FAIL |
|
|
Inspection was for units 305 and 357. Repair exit signs/emergency lights in both tenants. Provide annual inspection for the fire extinguishers in both tenants. Provide additional fire extinguisher near front (south end) of tenant 357. Sprinkler pendants are overspaced off of the south wall in the two existing offices of tenant 357(see approved plans). Repair the damaged electrical outlests. Provide sprinkler coverage beneath the south overhead door of tenant 357 because the door exceeds 4'-0". Remove the thumbturn locks from the restroom doors in tenant 305. Provide a racking permit for the 11'-6" racks located in tenant 305. Currently balloons, refrigerators, computers and toys (plastic) are being stored on wooden pallets within (floor level) the racks themselves. Storage is at 7'-0". Atleast two building columns have been positionded within the storage racks which requires sprinkler protection per NFPA 13. The duct smoke detectors in unit 305 are in a trouble condition and will need repaired. The fire alarm panel is in a trouble condition and will need repaired. Provide approved hardware on the south secondary exit door from tenant 305. Provide corrected upright fire sprinkler protection along both sides of the two new full height walls. Both sides of walls to be included.
|
BLD08-00126
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 10:08:03 AM | A | PASS |
|
|
fire life safety passed
|
BLD07-02896
| FIRE-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 8:36:16 AM | A | PASS |
|
|
fire life safety passed
|