Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00168 INSP-Final Inspection4/25/20124/25/20124/26/2012 9:50:54 AMPPASS
Permit finaled
BLD12-00458 FIRE-Final Inspection4/25/20124/25/20124/26/2012 9:34:43 AMPFAIL
Provide fire extinguisher with current inspection tag as discussed. Provide missing esch. rings on the sprinkler pendants. Remove the thumbturn dead bolt on the rear exit door. Provide address number(existing is badly faded). Provide the city approved drawings, including the small documents, for on site review.
BLD12-00481 FIRE-Final Inspection4/25/20124/25/20124/26/2012 8:31:00 AMPPASS
life safety passed
BLD06-02320 FIRE-Conference4/25/20124/25/20124/26/2012 8:23:18 AMACANC
Bob phone #: ###-####
FIR11-00543 INSP-Sprinkler Rough-in4/24/20124/25/20124/26/2012 8:06:36 AMPPART
Todays inspection was for Area E. See the approved plans for areas/rooms that are ok for cover. The entire area at remote area #3 needs to be resubmitted prior to approval for cover. Several of the 1" armovers have two to three times the fitting counts that are shown on the plans. The 1 1/4" branchline routing has changed with the installation of bull head tees to re-route the piping and the installation of 45 degree fittings to change elevations due to high ceilings. The wall layout has changed as well. I noted two areas that will be considered combustible concealed spaces that will need to be addressed.
FIR12-00161 INSP-Sprinkler Rough-in/Hydro4/25/20124/25/20124/25/2012 2:24:37 PMPFAIL
The standpipe hydro test failed due to a visible 2psi loss on five different guages/locations on the standpipe system.
BLD12-00850 FIRE-Final Inspection4/24/20124/25/20124/25/2012 10:36:49 AMAFAIL
The annual inspection for the fire sprinkler system is almost due. Resubmit actual floor plan to plan review. Needs to include all walls (temporary and existing). Repair the emergency lights. The audio/visual devices appear to be overspaced. There are roughly 6 devices for the entire space. Verification needs to be provided that the installed system is code compliant. If not code compliant modifications will need to be made.
FIR12-00168 INSP-Final Inspection4/25/20124/25/20124/25/2012 9:14:57 AMACANC
Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche
FIR12-00161 INSP-Sprinkler Rough-in/Hydro4/24/20124/25/20124/25/2012 8:27:18 AMAFAIL
Hydro test for the standpipe system failed due to a fitter draining the system as I documenting pressure on the fourth floor guages.