BLD16-00443 FIRE-Sprinkler Rough-in4/25/20164/25/20164/25/2016 12:51:09 PMPPASS
Fire life safety passed
FIR16-00193 INSP-Final Inspection4/25/20164/25/20164/25/2016 12:48:35 PMPFAIL
Will be able to final when I get verification that the SIN for the large orfice pendants was a type O and the pendants in the hardlids are changed to Intermediate Temp or verification that the supply diffuser puts out less than 100 degree heat as per NFPA 13 8.3.2.5 (9)
FIR16-00187 INSP-Sprinkler Rough-in4/22/20164/25/20164/25/2016 8:32:05 AMAPASS
Remaining piping is ok to cover.