BLD16-00443
| FIRE-Sprinkler Rough-in | 4/25/2016 | 4/25/2016 | 4/25/2016 12:51:09 PM | P | PASS |
|
|
Fire life safety passed
|
FIR16-00193
| INSP-Final Inspection | 4/25/2016 | 4/25/2016 | 4/25/2016 12:48:35 PM | P | FAIL |
|
|
Will be able to final when I get verification that the SIN for the large orfice pendants was a type O and the pendants in the hardlids are changed to Intermediate Temp or verification that the supply diffuser puts out less than 100 degree heat as per NFPA 13 8.3.2.5 (9)
|
FIR16-00187
| INSP-Sprinkler Rough-in | 4/22/2016 | 4/25/2016 | 4/25/2016 8:32:05 AM | A | PASS |
|
|
Remaining piping is ok to cover.
|