Inspections for the day of: Tuesday, April 25, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00741 INSP-Sprinkler Rough-in/Hydro4/24/20174/25/20174/25/2017 3:15:30 PMPFAIL
Tenting will need to be adjusted/added to cover area's of exposed piping in attic space on level 2. Batting insulation will need to be installed over fire sprinkler piping installed close to eaves, concern about blow in type insulation covering sprinkler piping in attic space.
NAF16-00084 INSP-Sprinkler Rough-in4/25/20174/25/20174/25/2017 1:36:21 PMPPART
Previously noted items for sway brace attachment corrected/completed, tenting/sway brace attachments approved for cover west of the fireplace, tenting still needs to be installed over the 6 inch supply main, main supply cannot be covered until tenting is inspected/passed.
FIR16-00760 INSP-Sprinkler Rough-in/Hydro4/24/20174/25/20174/25/2017 1:21:35 PMAPART
Hydrostatic test complete for levels 2 and 3, rough to cover inspection complete for level 2, level 2 approved for cover, partial cover approved for level 3, overhead fire sprinkler piping in attic space cannot be covered until tenting is installed and passed inspection.
BLD15-01130 FIRE-Final Inspection4/24/20174/25/20174/25/2017 12:03:24 PMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers will be mounted in discussed locations, knox box is in place, thumbturn deadbolts in common area doorways will be changed to double-keyed deadbolts. Final life fire safety inspection passed/complete.
FIR16-00606 INSP-Sprinkler Rough-in4/24/20174/25/20174/25/2017 9:39:14 AMAPART
Partial rough to cover inspection complete for overhead fire sprinkler piping on level 3, notated city approved drawings with green highlighter/red ink area's approved for cover.
BLD17-00449 FIRE-Final Inspection4/24/20174/25/20174/25/2017 8:32:54 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, space is a vanilla TI so fire extinguisher is in break room but not mounted. Final life fire safey inspection passed/complete.
FIR17-00119 INSP-Final Inspection4/24/20174/25/20174/25/2017 8:31:16 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00103 INSP-Final Inspection4/25/20174/25/20174/25/2017 8:30:33 AMAPASS
Final fire alarm inspection passed/complete
FIR17-00158 INSP-Final Inspection4/20/20174/25/20174/25/2017 7:24:43 AMAPASS
Final fire alarm inspection passed/complete
FIR17-00078 INSP-Final Inspection4/20/20174/25/20174/25/2017 7:24:12 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00126 INSP-Final Inspection4/24/20174/25/20174/25/2017 7:01:16 AMAPASS
Final fire alarm inspection passed/complete