FIR16-00741
| INSP-Sprinkler Rough-in/Hydro | 4/24/2017 | 4/25/2017 | 4/25/2017 3:15:30 PM | P | FAIL |
|
|
Tenting will need to be adjusted/added to cover area's of exposed piping in attic space on level 2. Batting insulation will need to be installed over fire sprinkler piping installed close to eaves, concern about blow in type insulation covering sprinkler piping in attic space.
|
NAF16-00084
| INSP-Sprinkler Rough-in | 4/25/2017 | 4/25/2017 | 4/25/2017 1:36:21 PM | P | PART |
|
|
Previously noted items for sway brace attachment corrected/completed, tenting/sway brace attachments approved for cover west of the fireplace, tenting still needs to be installed over the 6 inch supply main, main supply cannot be covered until tenting is inspected/passed.
|
FIR16-00760
| INSP-Sprinkler Rough-in/Hydro | 4/24/2017 | 4/25/2017 | 4/25/2017 1:21:35 PM | A | PART |
|
|
Hydrostatic test complete for levels 2 and 3, rough to cover inspection complete for level 2, level 2 approved for cover, partial cover approved for level 3, overhead fire sprinkler piping in attic space cannot be covered until tenting is installed and passed inspection.
|
BLD15-01130
| FIRE-Final Inspection | 4/24/2017 | 4/25/2017 | 4/25/2017 12:03:24 PM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers will be mounted in discussed locations, knox box is in place, thumbturn deadbolts in common area doorways will be changed to double-keyed deadbolts. Final life fire safety inspection passed/complete.
|
FIR16-00606
| INSP-Sprinkler Rough-in | 4/24/2017 | 4/25/2017 | 4/25/2017 9:39:14 AM | A | PART |
|
|
Partial rough to cover inspection complete for overhead fire sprinkler piping on level 3, notated city approved drawings with green highlighter/red ink area's approved for cover.
|
BLD17-00449
| FIRE-Final Inspection | 4/24/2017 | 4/25/2017 | 4/25/2017 8:32:54 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, space is a vanilla TI so fire extinguisher is in break room but not mounted. Final life fire safey inspection passed/complete.
|
FIR17-00119
| INSP-Final Inspection | 4/24/2017 | 4/25/2017 | 4/25/2017 8:31:16 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR17-00103
| INSP-Final Inspection | 4/25/2017 | 4/25/2017 | 4/25/2017 8:30:33 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR17-00158
| INSP-Final Inspection | 4/20/2017 | 4/25/2017 | 4/25/2017 7:24:43 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR17-00078
| INSP-Final Inspection | 4/20/2017 | 4/25/2017 | 4/25/2017 7:24:12 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR17-00126
| INSP-Final Inspection | 4/24/2017 | 4/25/2017 | 4/25/2017 7:01:16 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|