BLD18-04402
| FIRE-Final Inspection | 4/24/2019 | 4/25/2019 | 4/25/2019 3:07:48 PM | A | FAIL |
|
|
Provide city approved plans and small documents and repair or remove the west exit door exit sign.
Mike Phone #: ###-####
|
BLD19-01133
| FIRE-Final Inspection | 4/25/2019 | 4/25/2019 | 4/25/2019 2:32:35 PM | P | PASS |
|
|
life safety passed
Stephanie Phone #: ###-####
|
FIR19-00199
| INSP-Sprinkler Rough-in | 4/25/2019 | 4/25/2019 | 4/25/2019 1:16:25 PM | P | PASS |
|
|
The pendant heads in the hard lids/clouds are ok for cover. The tape will need to be removed from the uprights in the large Lobby prior to a final inspection.
Jessica Phone #: ###-####
|
FIR19-00215
| INSP-Sprinkler Rough-in | 4/24/2019 | 4/25/2019 | 4/25/2019 9:23:22 AM | A | PART |
|
|
See the city approved plans for apartments marked on the north half of the building where piping is ok for cover.
Gabe Garduno is the contact. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD17-02643
| FIRE-Final Inspection | 4/24/2019 | 4/25/2019 | 4/25/2019 9:13:35 AM | A | PASS |
|
|
Life safety passed.
Lin Phone #: ###-####
|
FIR18-00675
| INSP-Sprinkler Rough-in/Hydro | 4/24/2019 | 4/25/2019 | 4/25/2019 9:01:15 AM | A | FAIL |
|
|
Inspection was for all piping to the south of the dividing doors between the Cafeteria and Gym. Hydro test failed due to missing sprinkler heads, also piping size for the amount of heads at the south end of the corridor does not match plans. Two additional 90's and additional piping needs to be added to the Gym area hydraulic calculation.
CONTACT NAME IS JEFF. INSPECTION IS FOR TEN SPRINKLER HEADS. Phone #: ###-#### Inspection requested via web by Chris Green
|